Technical guideFree to readYear not stated

ProtectPlus M500: EN 11/2024 V1

AEG Power Solutions

AEG Power Solutions' ProtectPLUS M500 brochure lists the technical data of a VFI-SS-111 modular UPS scaling from 25 to 600 kVA with 25 kVA hot-swappable modules, 95.6% double-conversion and 98.5% ECO efficiency.

On this page

Overview

The brochure presents ProtectPLUS M500 as a transformerless, modular three-phase UPS designed for data centres, transportation, building infrastructure and light industry. A system starts at 25 kVA and grows with 25 kVA hot-swappable modules up to 600 kVA. One frame holds up to 8 modules (200 kVA) and up to 3 frames operate in parallel.

On architecture, each power module has independent hardware and control and there is no master/slave arrangement, so the failure of a single module does not stop the system. Control stays decentralised while modules run in parallel. The document links this design to a lower mean time to repair (MTTR). An optional 30 A charger module fits into a power module slot.

Electrical data are tabulated: input power factor 0.99, input THDi below 3% at 100% linear load, output voltage regulation of ±1% on linear load, output THDv below 1% on linear load and below 6% on nonlinear load. Output power factor is 1 and crest factor 3:1. Inverter overload capacity is 110% for 60 minutes, 125% for 5 minutes, 150% for 1 minute and above 150% for 200 ms.

For the battery line, nominal DC voltage is ±240 V (+/N/- connections), with 40 12 V lead-acid blocks as the default and any even number from 32 to 44 selectable. Recharge power is settable up to 20% of system power and temperature compensation is 3.0 mV/°C per cell. Operating temperature is 0-40 °C, noise at 1 m is 65 dB or less and protection is IP20. The document carries no binding warranty.

Key points

  1. Capacity range 25-600 kVA; one frame up to 200 kVA (8 modules), up to 3 frames in parallel.
  2. Frame 482 x 916 x 1550 mm, 160 kg; power module 25 kVA / 25 kW, 436 x 677 x 85 mm, 18 kg.
  3. AC/AC efficiency up to 95.6% in double conversion (VFI) and up to 98.5% in ECO mode (VFD).
  4. Input: 380/400/415 V, 3Ph+N+G, 304-478 V at full load, power factor 0.99, THDi below 3%.
  5. Output: ±1% regulation, THDv below 1% (linear) and 6% (nonlinear), power factor 1, crest factor 3:1.
  6. Overload: 110% for 60 min, 125% for 5 min, 150% for 1 min, above 150% for 200 ms.
  7. Battery line ±240 V DC; 40 blocks (even number 32-44), recharge up to 20% of system power, optional 30 A charger module.
  8. Operating 0-40 °C, storage -40 to 70 °C, humidity 0-95%; noise at most 65 dB at 1 m; IP20.
  9. Standards: IEC EN 62040-1 (safety), 62040-2 (EMC), 62040-3 (performance).

Using it in design

  • Compare the 200 kVA frame and 3-frame parallel (600 kVA) limits with the final room capacity and plan phasing in 25 kVA steps.
  • For N+1, size the module count as the peak load plus one 25 kVA module, and record the absence of a master/slave single point of failure in the risk analysis.
  • Check the 40-block (±240 V) default, the 32-44 block range, the 20% charge limit and temperature compensation against the project battery model.
  • Check generator compatibility with the input THDi (below 3%) and power factor of 0.99, and size cables and protection with the output PF of 1.
  • Use the overload curve (110/125/150%) as an input to protection and bypass selectivity studies.
  • Compare the IP20 cabinet and 0-40 °C operating range with the room environment.

Who should read it

Electrical designers, specification engineers and capacity planners selecting UPS systems for mid-size and large data centre projects.

Document contents

  1. Features and benefits
  2. Typical applications
  3. Specifications
  4. Power module
  5. Input
  6. Output
  7. Battery line
  8. User interface
  9. Environmental
  10. Standards and certifications

Publication details

Authors
AEG Power Solutions
Publisher
AEG Power Solutions
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

AEG Power Solutions ProtectPlus M500: EN 11/2024 V1. AEG Power Solutions. https://www.aegps.com/en/wp-content/uploads/2026/01/AEGPS_LEA_ProtectPlus_M500_2025_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.