AEG ProtectPlus S500: 250-600 kVA Three-Phase Transformer-Less UPS
Original title AEG Protect Plus S500 English datasheet 04/2021 V1, p.2
AEG Power Solutions
AEG Power Solutions ProtectPlus S500, a 250-600 kVA transformer-less three-level IGBT UPS: 95.2-95.7% double-conversion efficiency, up to 99% in ECO mode, input THDi below 3% and up to 8 units in parallel.
On this page
Overview
The document is a two-page brochure for the ProtectPlus S500 family. The product is a monolithic transformer-less three-level IGBT UPS rated 250, 300, 400, 500 and 600 kVA (kW), classed VFI SS 111. AC/AC efficiency in double conversion is 95.2 to 95.7%; in ECO mode it can exceed 99% and in Smart ECO mode 98% at nominal load. Input power factor is above 0.99 and input THDi is below 3% with a full linear load.
Output power factor reaches 1 (0-35 °C) and the load range from 0.5 inductive to 0.5 capacitive needs no derating. Output THDv is below 1% on a linear load. The inverter carries 125% for 10 minutes and 150% for 60 seconds; the bypass line carries 125% continuously. The battery line is nominally 480 Vdc with 40 blocks of 12 V by default; 38 to 44 blocks are settable, 32 to 44 with derating to PF 0.8. VRLA and Li-ion are supported and charge current is 25-100 A.
Dimensions are 1000 x 900 x 1950 mm and 750 kg for 250-400 kVA and 1400 x 900 x 1950 mm and 1100 kg for 500-600 kVA. Operating temperature is 0-40 °C (up to 50 °C with derating), no altitude derating below 1500 m, noise below 75 dB at 1 m. Standards are IEC EN 62040-1, -2 and -3. The maker states the data carry no binding warranty, and ECO and some values are conditional.
Key points
- 250, 300, 400, 500, 600 kVA; kW = kVA (output PF up to 1); VFI SS 111.
- AC/AC efficiency 95.2-95.7% in double conversion; >99% in ECO mode, >98% in Smart ECO mode (nominal load).
- Input PF >0.99, input THDi <3%; input voltage 380/400/415 V.
- Overload: inverter 125% for 10 min, 150% for 60 s; bypass 125% continuous, 150% for 10 min.
- Nominal battery voltage 480 Vdc, 40 blocks of 12 V (38-44 settable), charge current 25-100 A.
- Up to 8 units in parallel; static and maintenance bypass standard.
- 250-400 kVA: 1000 x 900 x 1950 mm, 750 kg; 500-600 kVA: 1400 x 900 x 1950 mm, 1100 kg.
- Operation 0-40 °C (to 50 °C with derating), no derating below 1500 m, noise <75 dB.
Using it in design
- In a data-hall UPS room, weigh the ECO and Smart ECO efficiency gain against the lower protection class in those modes.
- Use input THDi <3% and PF >0.99 to reduce generator oversizing and the need for input filters.
- Select battery block count (38-44) together with DC bus voltage and PF derating.
- Use the 750 and 1100 kg weights for floor loading and the 1000 or 1400 mm width for layout.
- Plan paralleled systems against the 8-unit limit.
Who should read it
Electrical engineers selecting UPS units for medium and large data centres and critical facilities.
Document contents
- Features and benefits
- Typical applications
- Specifications: mains input, bypass, output, battery, user interface
- General and standards
Publication details
- Authors
- AEG Power Solutions
- Publisher
- AEG Power Solutions
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
AEG Power Solutions AEG Protect Plus S500 English datasheet 04/2021 V1, p.2. AEG Power Solutions. https://www.upss.ro/web/b2b/images/uploaded/products/PDF/AEG_PROTECT_PLUS_S500_EN_1.PDF
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.