Technical guideFree to read2019

Airedale LogiCool InRak 600 mm In-Row IT Cooling Technical Manual (2019)

Original title LogiCool InRak 600 technical manual

Airedale

Airedale's September 2019 InRak technical manual: 600 mm wide in-row IT cooling in single or dual circuit chilled water and DX (R410A) versions, with EC fans, N+1 fan redundancy and normal operation at 75% airflow.

On this page

Overview

The manual contains installation, commissioning and maintenance information and technical data for Airedale LogiCool InRak in-row IT cooling units. The model code states the operating mode (C0 single circuit chilled water, CC dual circuit chilled water, DX versions) and the case width (millimetres x 10 = 600 mm). Units draw hot aisle air at the rear and supply the cold aisle with 310 mm backward curved centrifugal fans with EC motors and inlet rings.

Redundancy features stand out: hot-swappable fans and dual power inputs. With the optional N+1 fan redundancy the unit normally runs at 75 percent airflow; if a fan fails, the remaining healthy fans speed up to 100 percent to deliver full design airflow. Negative air pressure at the server outlet in the hot aisle prevents backwash of hot air. In the chilled water version an efficient coil is standard and 2- or 3-way valves, isolation valve and solenoid valve are optional; the DX version has a fixed speed scroll compressor as standard.

Technical data tables give gross total cooling and power input by return air condition: for example at 25 °C/42% RH, gross total cooling is 18.83-21.13 kW at some water conditions with power input of 4.43-9.69 kW; at 30 °C/32%, 26.60-29.18 kW and 6.79-14.99 kW; at 35 °C/24%, 30.13-35.25 kW; at 40 °C/18%, 30.30-39.61 kW. Capacity rises as return air temperature rises. Glycol is recommended for supply water of 5 °C or below.

The manual also covers charging R410A in liquid phase only, R410A-suitable manifold and recovery equipment, condensate pump performance, regulatory notes (Legionella prevention, COSHH) and warranty and maintenance terms; the standard warranty is 12 months on non-consumable parts and conditional on maintenance.

Key points

  1. Case width is 600 mm; versions are single circuit chilled water (C0), dual circuit chilled water (CC) and DX (R410A).
  2. 310 mm backward curved EC fans; hot-swappable fans and dual power inputs.
  3. With optional N+1 fan redundancy, normal operation is at 75 percent airflow; on fan failure the remaining fans go to 100 percent.
  4. Negative pressure at the server outlet in the hot aisle prevents hot air backwash.
  5. Gross total cooling is about 18.83-21.13 kW at 25 °C return air and about 30.30-39.61 kW at 40 °C; capacity rises with return temperature.
  6. Power input in the tables ranges from 4.43 kW to 15.08 kW.
  7. Glycol is recommended for supply water of 5 °C and below.
  8. The DX version has a fixed speed scroll compressor as standard; R410A is charged in liquid phase only.
  9. Standard warranty is 12 months for non-consumable parts and conditional on maintenance.

Using it in design

  • Read in-row capacity against return air temperature; in a contained aisle 35-40 °C return air raises capacity markedly, so define this condition realistically in the design.
  • With N+1 fan redundancy, include 75 percent normal airflow and the rise to 100 percent on failure in power and noise calculations.
  • In the chilled water version, if supply water is 5 °C or below, set glycol ratio and capacity correction.
  • Consider the dual circuit version for circuit redundancy by feeding it from two independent chilled water sources.
  • Check condensate pump head together with pipe losses and vertical lift.

Who should read it

Engineers and technicians installing, commissioning and operating in-row cooling units.

Document contents

  1. Warranty, commissioning and maintenance
  2. Safety and refrigerant (R410A) handling
  3. Model code and general features
  4. Standard and optional features (fan redundancy, condensate pump)
  5. Cooling mode: chilled water
  6. Technical data: chilled water
  7. Technical data: dual circuit chilled water

Publication details

Authors
Airedale
Publisher
Airedale
Year
2019
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Airedale (2019). LogiCool InRak 600 technical manual. Airedale. https://www.airedale.com/wp-content/uploads/2020/01/TM_INRAK_600_7462807_V1.17.2_09_2019.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.