Technical guideFree to read2019

Airedale OptiChill FreeCool OFC R134a Free Cooling Chiller Technical Manual (750-1250 kW, 2019)

Original title OptiChill FreeCool technical manual7197700

Airedale

Airedale's April 2019 OptiChill FreeCool technical manual: R134a air-cooled chiller with semi-hermetic twin screw compressors and a free cooling coil, 750-1,250 kW class, with 8 capacity steps from 20 to 100 percent.

On this page

Overview

The manual holds technical data, installation and maintenance information for the 750-1,250 kW class Airedale OptiChill FreeCool (OFC) R134a air-cooled chiller family. Units use semi-hermetic twin screw compressors and 2- or 3-row free cooling coils with 'regular quiet' and 'extra quiet' fan options. The model code (for example OFC084R20-76HL2) encodes capacity, refrigerant, row count and noise class; capacity steps are 20, 30, 40, 55, 65, 80, 90 and 100 percent.

Technical tables give values declared under Ecodesign requirements: rated cooling capacity (for example 718.5 kW on one model) and declared capacity at 35, 30, 25 and 20 °C ambient. For the same model, declared capacity is 715.2 kW at 35 °C, 526.1 kW at 30 °C, 337.0 kW at 25 °C and 148.0 kW at 20 °C; that is, mechanical capacity falls at lower ambient while the free cooling share rises. On larger models rated capacity appears at about 899.8 kW. Other tables cover compressor currents, recommended fuse size (710-800 A) and sound data.

Application notes: glycol is recommended if supply water is +5 °C or below or static water may freeze. At ambient below 0 °C, glycol of suitable concentration must give protection at least 3 K below ambient freeze point, the water/glycol solution must circulate constantly and pumps must run in shutdown periods when ambient is within 3 K of the freeze point. R134a has a GWP of 1,430 under EN 378-1:2016 and is charged in liquid phase only. The manual also has installation, commissioning, maintenance and Legionella notes.

Key points

  1. 750-1,250 kW class; semi-hermetic twin screw compressors, R134a, 2- or 3-row free cooling coils.
  2. Capacity steps are 20, 30, 40, 55, 65, 80, 90 and 100 percent.
  3. Example model: rated cooling capacity 718.5 kW; declared 715.2 kW at 35 °C, 526.1 at 30 °C, 337.0 at 25 °C and 148.0 kW at 20 °C.
  4. A larger model has a rated capacity of about 899.8 kW.
  5. EER is defined as DX cooling output over compressor plus fan input power.
  6. Glycol is recommended for supply water of +5 °C and below; below 0 °C ambient, protection at least 3 K under the freeze point is required.
  7. Pumps must run in shutdown periods when ambient is within 3 K of the freeze point.
  8. R134a has a GWP of 1,430 (EN 378-1:2016, 100 year).
  9. Recommended mains fuse sizes range from 560 to 800 A.

Using it in design

  • When selecting a free cooling chiller, use the declared capacity table at 35/30/25/20 °C ambient, not only rated capacity, to compute the mechanical and free cooling shares from the annual temperature distribution.
  • On sites that fall below 0 °C, set glycol concentration at least 3 K below the freeze point and write the shutdown pump operation strategy into the design.
  • Map the 8 capacity steps to the hall part-load profile and ask for efficiency per step.
  • Record the R134a charge and GWP of 1,430 in the project for F-gas and refrigerant regulation.
  • Pass recommended fuse sizes and compressor running currents (for example 186.1/159.5 A) to electrical design.

Who should read it

Mechanical engineers selecting and commissioning free cooling chillers for large data centre chilled water plants.

Document contents

  1. Warranty, commissioning and maintenance
  2. Safety and R134a handling
  3. Chilled water and glycol use
  4. Model coding
  5. Technical data (declared capacity, EER, compressor, electrical)
  6. Sound data
  7. Dimensions and weights

Publication details

Authors
Airedale
Publisher
Airedale
Year
2019
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Airedale (2019). OptiChill FreeCool technical manual7197700. Airedale. https://airedale.com/wp-content/uploads/2020/01/TM_OPTICHILL_FREECOOL_R134a_750-1250kW_7197700_v1.11.1_04_2019.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.