Maximizing cooling and heat reuse: How AlfaQ heat exchangers are revolutionizing the way we connect data centers to district heating
Original title Maximizing Cooling and Heat Reuse: How AlfaQ Heat Exchangers Are Revolutionizing the Way We Connect Data Centers to District Heating
Alfa Laval
Alfa Laval's HeatChain case story reports data-centre waste heat delivered to district heating at 75-80°C in Finland, with 50 GWh in 2025, an average PUE of 1.04 and a 64% energy reuse factor.
On this page
Overview
This Alfa Laval case story describes Finland-based HeatChain's modular, prefabricated 'data boiler' plants. HeatChain supplies the infrastructure for facilities where IT companies run their own servers: liquid cooling for high-performance computing (HPC) and delivery of waste heat to district heating networks. The plants use Alfa Laval AlfaQ plate heat exchangers.
The core problem is temperature level: typical data-centre waste heat is at 25-50°C, and lifting it to the 70-90°C+ needed for district heating requires energy-intensive heat pumps. HeatChain uses liquid cooling and HPC computers as the heat source to produce heat at 75-80°C, which is passed directly to the network without heat pumps. To keep temperature loss low, the exchangers are designed to run at a very small logarithmic mean temperature difference (LMTD).
On the product side, standard AlfaQ solutions were supplied for three standard unit sizes (1 MW, 2 MW and 5 MW); all exchangers are AHRI certified. They operate in pairs, with one for backup cooling. Alfa Laval has delivered two kinds of AlfaQ exchanger to 10 HeatChain data centres in Finland, and new facilities have historically gone live roughly every 2 months.
The measured results come from facilities the company runs itself: in 2025 facilities owned or operated by HeatChain delivered 50 GWh of district heating energy, achieved 3650 tons of CO2 reduction, an average annualised PUE of 1.04 and an annualised Energy Reuse Factor (ERF) of 64%. The document is a manufacturer case story and carries no independent verification.
Key points
- Typical data-centre waste heat is 25-50°C; district heating needs 70-90°C and above.
- The HeatChain system delivers heat at 75-80°C through liquid cooling, avoiding heat pumps.
- Standard units are 1 MW, 2 MW and 5 MW; exchangers are AHRI certified and run in pairs with one as backup.
- Alfa Laval has delivered two kinds of AlfaQ exchanger to 10 HeatChain data centres.
- In 2025, 50 GWh of district heating energy and 3650 tons of CO2 reduction are reported.
- Average annualised PUE is 1.04; annualised ERF is 64%.
- New facilities have historically gone live about every 2 months.
- A running 4 MW data boiler in Outokumpu is shown as an example.
Using it in design
- When planning heat recovery, compare the fluid temperature level (75-80°C) with the network's acceptance temperature; lower temperatures need heat pumps.
- Size the heat exchanger for a very small LMTD; the approach temperature difference sets the losses between source and network.
- Plan exchangers in pairs so one serves as backup cooling.
- Report PUE and ERF together; a 64% ERF shows the share of energy reused.
- For modular (1, 2, 5 MW) plants, choose standard unit sizes at the start to shorten commissioning.
Who should read it
Mechanical designers, energy planners and investment decision makers assessing connecting data-centre waste heat to district heating.
Document contents
- Maintaining high temperatures with minimal energy loss
- Partnership and trust
- An AHRI certified solution for highly efficient heat transfer
- About HeatChain
- Walking the talk: operating results
- Why data center heat reuse is so in demand
Publication details
- Authors
- Alfa Laval
- Publisher
- Alfa Laval
- Year
- Year not stated
- Document number
- 100022801-1-EN 2601
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public manufacturer document or page inspected. No document-specific redistribution permission established; retain metadata and original short summaries only.
Citation
Alfa Laval Maximizing Cooling and Heat Reuse: How AlfaQ Heat Exchangers Are Revolutionizing the Way We Connect Data Centers to District Heating. Alfa Laval. 100022801-1-EN 2601. https://assets.alfalaval.com/documents/pcf929a19/alfa-laval-maximizing-cooling-and-heat-reuse-how-alfaq-heat-exchangers-are-revolutionizing-the-way-we-connect-data-centers-to-district-heating.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.