Availability Analysis of Redundant and Replicated Cloud Services with Bayesian Networks
arXiv / author manuscript · Otto Bibartiu, Frank Dürr et al.
An arXiv paper by University of Stuttgart and Bosch researchers builds a Bayesian network that models infrastructure and network failures together, including cascading and common-cause failures; the method suits services of up to 30 instances.
On this page
Overview
The paper starts from the point that as modern data centres grow more complex, failures are no longer rare and availability requirements are met by fault tolerance mechanisms. Earlier Bayesian network work modelled either infrastructure or communication failures separately; this work treats both together. A component failure spreads in cascade to dependent components, and common-cause failures can affect several components at once.
The approach is a high-level description made of three sub-models: an infrastructure failure model, a network model, and a model of the service's fault tolerance semantics (redundant or replicated, k-out-of-n and voting-based replication). Infrastructure fault dependencies are expressed as a directed acyclic graph with a static fault tree per component. The description is translated automatically into a Bayesian network, so the engineer chooses the component granularity.
The evaluation uses a small infrastructure of 19 components and a large one of three data centres, each with 40 hosts, 20 network components and 100 additional infrastructure components per data centre, 440 components in total. Component availabilities are sampled from Beta(10000, 1), meaning an average of 1 hour of downtime in 10,000 hours. A service counts as available when a majority of instances work.
Results show that memory use grows exponentially in the conditional probability tables and that the basic approach is practical only for services of up to 30 instances; scalable AND/OR and k-out-of-n equivalents lift that limit. The discussion notes that the largest model, with 300 instances, took about an hour to build, that inference can then be run independently, and that obtaining accurate failure probability data is the main practical difficulty.
Key points
- The model is presented as handling infrastructure and network failures together, including cascading and common-cause failures, in one Bayesian network.
- Three sub-models: infrastructure failure model, network model and service fault tolerance model.
- Fault dependencies are defined by a directed acyclic graph and a static fault tree per component.
- The small evaluation infrastructure has 19 components; the large one has 3 data centres, 40 hosts each and 440 components in total.
- Component availability is sampled from Beta(10000, 1); average downtime of 1 hour per 10,000 hours.
- Because of exponential memory growth in conditional probability tables, the basic approach is practical for services up to 30 instances.
- Scalable AND/OR and k-out-of-n equivalents overcome the memory limit.
- The largest model of 300 instances takes about an hour to build; inference is then independent.
- For services with 3-7 replicas, exact inference is feasible; approximate inference is used for many replicas.
Using it in design
- Add common-cause failures (same power feed, same cooling loop, same network path) explicitly as dependencies in the availability model; otherwise redundancy benefit is overstated.
- For multi-site replicated services, assess network path failures in the same model as server failures.
- Where component failure probability data is thin, test the model parameters with sensitivity analysis.
- Before adding more redundant replicas, remove the shared dependencies the model reveals, such as a common data centre infrastructure component.
- To limit computation, include only the essential routes in the model, and use the scalable gate equivalents above 30 instances.
Who should read it
Reliability engineers and researchers modelling data centre and cloud service availability.
Document contents
- Introduction
- System Model
- High Level Model Description
- Bayesian Network Model
- Evaluation
- Discussion
- Related Work
Publication details
- Authors
- Otto Bibartiu; Frank Dürr; Kurt Rothermel; Beate Ottenwälder; Andreas Grau
- Publisher
- arXiv / author manuscript
- Year
- 2023
- Document number
- arXiv:2306.13334v1
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
arXiv v1 abstract and PDF opened. Its licence link is arXiv non-exclusive distribution permission, not a general reuse licence. Related Wiley journal DOI 10.1002/qre.3414 was blocked; no journal licence transferred to this manuscript.
Citation
Otto Bibartiu; Frank Dürr; Kurt Rothermel; Beate Ottenwälder; Andreas Grau (2023). Availability Analysis of Redundant and Replicated Cloud Services with Bayesian Networks. arXiv / author manuscript. arXiv:2306.13334v1. https://doi.org/10.48550/arXiv.2306.13334
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.