2011 Thermal Guidelines for Liquid Cooled Data Processing Environments (ASHRAE TC 9.9 White Paper)
ASHRAE (announcement via HPAC Engineering) · ASHRAE TC 9.9
The 2011 TC 9.9 white paper that first defined the W1-W5 facility-water classes for liquid-cooled IT; content here is taken from trade-press coverage.
On this page
Overview
This white paper, published by ASHRAE TC 9.9 in 2011, introduced facility-water temperature classes (W1-W5) for liquid-cooled data processing environments. ASHRAE billed it as the first vendor-neutral thermal guideline for such environments and offered it as a free download. It followed the May 2011 air-cooling paper on expanded data center classes.
The classes are defined by facility-water supply temperature: W1 at 2-17 C, W2 at 2-27 C, W3 at 2-32 C, W4 at 2-45 C and W5 above 45 C. Their purpose is to enable full-time economizers for many applications and climates. The paper also covers condensation, operation, water flow rate, pressure, velocity and quality, interface connections and heat-rejection devices.
The information here comes from the trade-press announcement (HPAC); the ASHRAE white paper itself was not read. Class boundaries were later renamed or revised in subsequent editions, so current values should be taken from ASHRAE's liquid cooling guidelines in force.
Key points
- Class W1 facility water supply is 2-17 C.
- Class W2 is 2-27 C and class W3 is 2-32 C.
- Class W4 is 2-45 C and class W5 is above 45 C.
- Billed by ASHRAE as the first vendor-neutral thermal guideline for liquid-cooled data processing environments; free download.
- The classes are intended to enable full-time economizers for many applications and climates.
- Condensation, operation, water flow rate, pressure, velocity and quality are covered.
- Interface connections and heat-rejection devices are also addressed.
- It followed the May 2011 air-cooling paper on expanded data center classes.
Using it in design
- In liquid-cooling design, tag facility water loops by W-class, noting that later editions may rename or revise them.
- Combine with climate data to check whether chiller-less operation is feasible.
- Include condensation risk and water quality requirements in the facility water specification.
Who should read it
Mechanical designers choosing facility-water temperature and heat rejection for liquid-cooled IT.
Related standards
- ASHRAE Liquid Cooling Guidelines
Publication details
- Authors
- ASHRAE TC 9.9
- Publisher
- ASHRAE (announcement via HPAC Engineering)
- Year
- 2011
- Document number
- TC 9.9 White Paper
- Document language
- English
- Source type
- Standard
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Facts from trade-press article (public web page, no open licence); ASHRAE white paper itself not read. Citation only.
Citation
ASHRAE TC 9.9 (2011). 2011 Thermal Guidelines for Liquid Cooled Data Processing Environments (ASHRAE TC 9.9 White Paper). ASHRAE (announcement via HPAC Engineering). TC 9.9 White Paper. https://www.hpac.com/archive/article/20925053/ashrae-introduces-thermal-guidelines-for-liquid-cooled-data-processing-environments
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
