Flow Indicator: Operating Manual
Original title Akış Göstergesi: Kullanım Kılavuzu
Hacı Ayvaz Endüstriyel Mamuller
Ayvaz's March 2019 flow indicator manual: a visual indicator for DN15-DN50 lines with limits of 16 bar and 150 °C, installation rules and isolation, depressurisation and cooling steps before maintenance.
On this page
Overview
The manual explains safe use of a flow indicator, an element for visually monitoring flow in closed pipe circuits. It is fitted before and after steam traps to watch for steam leaks and used in food and pharmaceutical industries for visual fluid checks. Operating conditions are a maximum of 16 bar, a maximum of 150 °C and a nominal size from DN15 (1/2 inch) to DN50 (2 inch). Warning signs must be placed at touchable points where fluid temperature is 60 °C or above.
The installation section requires the unit to stay within the manual's pressure, temperature and fluid limits, connecting parts to be concentric, in threaded connections the thread count at the connection to be lower than on the indicator, pipes to be clamped so they do not sag, and flange bolts tightened in a cross pattern. Before installation, fluid should be flushed out for a while to clear dirt, flow direction respected and the indicator insulated where cold would affect operating temperature.
In operation the glass is tempered soda-lime glass that does not shatter on breakage; with borosilicate glass and gasket on request, the operating temperature can be raised to 200 °C. Before maintenance the indicator must be isolated from supply and return lines, pressure safely released and the unit allowed to cool. For cleaning, close the lower then the upper shut-off valve, drain the fluid through the drain plug into a suitable container, clean the inside with a soft brush and the outside with a damp cloth, and avoid aggressive cleaners and hard objects. Body and cover are GG-25 cast iron. At end of life the unit goes to metal recycling.
Key points
- Maximum working pressure 16 bar, maximum working temperature 150 °C, nominal size DN15 (1/2 inch) to DN50 (2 inch).
- Warning signs are required at touchable points when fluid temperature is 60 °C or above.
- The indicator is also used before and after steam traps to monitor steam leaks.
- In threaded connections the thread count at the connection must be lower than on the indicator.
- In flanged connections tighten bolts in a cross pattern; clamp pipes so they do not sag.
- Flush fluid for a while before installation and respect flow direction.
- Tempered soda-lime glass does not shatter; borosilicate glass and gasket raise the limit to 200 °C.
- Before maintenance, isolate from supply and return lines, release pressure and let it cool.
- Body and cover are GG-25 cast iron.
Using it in design
- For circuits needing visual flow confirmation (cooling water, condensate), compare the 16 bar and 150 °C limits and the DN15-DN50 range with the pipe class.
- Place the indicator where it is easy to maintain, with coaxial connections and correct flow direction; support pipes with clamps.
- Provide shut-off valves and a drain plug on both sides so line pressure release and isolation can be done safely for maintenance.
- Add insulation and warning signs to the specification for cold areas and for hot lines above 60 °C.
- State in the design document that the indicator gives visual monitoring only and does not replace safety or emergency devices.
Who should read it
Mechanical engineers and technicians selecting, installing and maintaining flow indicators on cooling and process lines.
Document contents
- General Information
- General Safety and Product Information
- Safety and Environmental Instructions
- Transport, Packaging and Storage
- Installation
- Operation
- Maintenance and Cleaning
- Disassembly, Return for Service and Decommissioning
- Technical Drawing
- Outer Cover and Zones
Publication details
- Authors
- Hacı Ayvaz Endüstriyel Mamuller
- Publisher
- Hacı Ayvaz Endüstriyel Mamuller
- Year
- 2019
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public manufacturer documentation inspected. No redistribution permission established. Metadata and original brief summaries only; local downloads are research evidence, not a redistribution package.
Citation
Hacı Ayvaz Endüstriyel Mamuller (2019). Akış Göstergesi: Kullanım Kılavuzu. Hacı Ayvaz Endüstriyel Mamuller. https://www.ayvaz.com/wp-content/pdf/kullanim_talimatlari/Akis_Gostergesi.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
