How to set up a system of DGC-2020HDs to achieve Generator and Group Breaker Control
Basler Electric · Denny Raymond
A 2022 Basler Electric application guide describing the controller roles, settings and logic needed to coordinate paralleled generators with a downstream group tie breaker.
On this page
Overview
The guide explains how a system of DGC-2020HD controllers achieves generator and group breaker control. The example assigns one controller to each generator and a separate controller to the group tie breaker, and the controllers are linked by Ethernet.
The tie-breaker controller does not directly issue raise/lower adjustments to the generators; it communicates with the generator controllers. This keeps the roles separate and leaves the paralleling logic in the generator controllers.
Key points
- The example has one controller per generator.
- A separate controller is assigned to the group tie breaker.
- The controllers are linked by Ethernet.
- The tie-breaker controller does not directly give raise/lower adjustments to a generator.
- The tie-breaker controller communicates with the generator controllers.
Using it in design
- In a paralleled generator system, draw the separate controller roles per generator and for the group breaker on the schematic.
- Define the Ethernet topology and redundancy between controllers in the network design.
- In commissioning tests, verify that speed and voltage adjustment commands come only from the generator controllers.
Who should read it
Electrical engineers designing and commissioning generator paralleling and group breaker control.
Publication details
- Authors
- Denny Raymond
- Publisher
- Basler Electric
- Year
- 2022
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public manufacturer source inspected. No redistribution permission established. Metadata and original brief summaries only; local files are research evidence, not a redistribution package.
Citation
Denny Raymond (2022). How to set up a system of DGC-2020HDs to achieve Generator and Group Breaker Control. Basler Electric. https://www.basler.com/resource-hub/application-guide/HowtoSetUpaSystemofDGC-2020HDstoAchieveGeneratorandGroupBreakerControl.pdf?_nonce=fa914ebfe0
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.