Technical guideFree to read2026

2026 Seismic Hazard Maps for the UK Region

British Geological Survey

British Geological Survey 2026 seismic hazard maps give PGA and spectral acceleration for five return periods from 95 to 5000 years; at 475 years PGA is about 0.04 g across much of the offshore EEZ.

On this page

Overview

The work, published by the British Geological Survey (BGS), provides hazard maps for peak ground acceleration (PGA) and spectral acceleration at 0.15 s (6.66 Hz), 0.2 s (5 Hz) and 1.0 s (1.0 Hz) with 5% damping for the UK, the Channel Islands and the UK offshore Exclusive Economic Zone. The maps use the 2024 offshore seismic hazard model and a Monte Carlo-based probabilistic seismic hazard assessment. They are estimated for five return periods: 95, 475, 1100, 2475 and 5000 years, corresponding to roughly 41%, 10%, 5%, 2% and 1% probability of exceedance in 50 years.

The maps confirm that seismic hazard in and around the UK is generally low by worldwide standards, and increases slightly in regions of higher observed seismic activity: North Wales, the Welsh Marches, the northern North Sea and the southern North Sea around Dogger Bank, where the largest instrumentally recorded earthquake (5.9 Mw) occurred. For example, at a 475-year return period the PGA hazard is about 0.04 g for much of the offshore EEZ.

The 2026 maps supersede the 2020 national maps and are the current reference hazard model for the UK. They underpin the forthcoming UK National Annex to the second-generation Eurocode 8 and give a consistent basis for seismic design, offshore infrastructure planning, risk assessment and evaluation of induced seismicity from industrial activities such as carbon capture and storage. The maps are not a substitute for a site-specific hazard assessment where one is required.

Key points

  1. PGA and spectral acceleration maps at 0.15 s, 0.2 s and 1.0 s with 5% damping.
  2. Five return periods: 95, 475, 1100, 2475 and 5000 years (about 41%, 10%, 5%, 2%, 1% exceedance in 50 years).
  3. At a 475-year return period PGA is about 0.04 g across much of the offshore EEZ.
  4. Hazard is low by worldwide standards, rising slightly in North Wales, the Welsh Marches and the northern and southern North Sea.
  5. The largest instrumentally recorded earthquake is 5.9 Mw in the Dogger Bank area.
  6. The maps supersede the 2020 national maps and underpin the UK National Annex to second-generation Eurocode 8.

Using it in design

  • For UK sites take seismic design input from these maps and state the design return period (for example 475 years) in project criteria.
  • In North Wales, the Welsh Marches and around the North Sea, where hazard rises, apply extra care in site selection and in structure and equipment anchorage design.
  • Remember the maps do not replace site-specific assessment; commission a site-specific hazard study for critical facilities where required.
  • When the Eurocode 8 UK National Annex is published, align design parameters with it.

Who should read it

Data-centre developers, structural engineers and risk analysts siting and designing facilities in the UK.

Publication details

Authors
British Geological Survey
Publisher
British Geological Survey
Year
2026
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Publisher public source inspected. No document-specific commercial redistribution permission established; metadata and original short summaries only.

Citation

British Geological Survey (2026). 2026 Seismic Hazard Maps for the UK Region. British Geological Survey. https://www.earthquakes.bgs.ac.uk/hazard/UKhazard2026.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Redundancy scenarios in SoSo CAD

Compare normal operation with equipment failures and see served loads and capacity shortfalls in the same view.

Normal operation and failure scenario comparison in SoSo CAD

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.