Liquid-to-Liquid and Liquid-to-Air Coolant Distribution Units for High Performance Data Centers
Original title Liquid-to-Liquid and Liquid-to-Air Coolant Distribution Units for High Performance Data Centers (CDU Comparison)
Boyd · Boyd Corporation
Boyd's CDU comparison tabulates capacity, flow, filtration and power for in-rack liquid-to-air (22 and 32 kW), in-rack liquid-to-liquid (110 and 300 kW) and in-row liquid-to-liquid (1,100, 2,300 and 2,000 kW) units.
On this page
Overview
The document compares Boyd's CDU range in three groups: in-rack liquid-to-air, in-rack liquid-to-liquid and in-row liquid-to-liquid. Each table gives nominal cooling capacity, secondary (TCS) fluid temperature range, flow, fluid type, dimensions, weight, power input, communication protocols and compliance. The latest high-performance models are offered under NDA.
Among in-rack liquid-to-air units, the RAA22-10U19 gives 22 kW at 24 °C approach (up to 50 LPM) and the RAA32-10U21 gives 32 kW at the same approach (up to 70 LPM); TCS temperature range is 25-50 °C, power input single-phase 100-240 VAC at up to 1.6 and 2.6 kW. In-rack liquid-to-liquid RAL110-04U19 gives 80 kW at 8 °C and 110 kW at 11.5 °C (80 LPM, 1.44 bar); RAL300-04U21 gives 160 kW at 5 °C and 300 kW at 9 °C (160 LPM, 1.7 bar) and runs on 48 VDC.
In-row units: ROL1100-48U32 gives 550 kW at 4 °C ATD and 1,100 kW at 8 °C (473 LPM), ROL2300-48U40 gives 1,150 kW at 4 °C and 2,300 kW at 8 °C (1,514 LPM), ROL4000-48U65 gives 2,000 kW at 3 °C ATD (1,893 LPM). Filtration is 50 or 25 micron (TCS) and 500 micron (FWS); the data is for N+1 pump redundancy, and more flow and capacity are available with all pumps running.
The document also presents Boyd's component ecosystem (cold plates, manifolds, leak detectors, quick disconnects) and a portable rack emulator simulating heat loads up to 250 kW. Data is indicative and the manufacturer gives no warranty.
Key points
- In-rack liquid-to-air: RAA22-10U19 22 kW, RAA32-10U21 32 kW (24 °C approach); TCS temperature 25-50 °C.
- In-rack liquid-to-liquid: RAL110-04U19 80 kW (8 °C) and 110 kW (11.5 °C approach); RAL300-04U21 160 kW (5 °C) and 300 kW (9 °C).
- RAL110 flow 80 LPM at 1.44 bar; RAL300 160 LPM at 1.7 bar; RAL300 runs on 48 VDC.
- In-row: ROL1100 550/1,100 kW (4/8 °C ATD), ROL2300 1,150/2,300 kW (4/8 °C), ROL4000 2,000 kW (3 °C ATD).
- In-row flows are 473, 1,514 and 1,893 LPM; dry weights 622, 1,032 and about 2,155 kg.
- Filtration: ROL1100 50 micron TCS and 500 micron FWS; ROL2300 and ROL4000 25 micron TCS and 500 micron FWS.
- Communication: Modbus TCP/IP, BACnet/IP, SNMPv3 and optional Redfish.
- Data is for N+1 pump redundancy; the rack emulator simulates heat loads up to 250 kW.
Using it in design
- Read CDU capacity at a matching approach temperature (ATD): the same unit gives 550 kW at 4 °C ATD and 1,100 kW at 8 °C ATD.
- Consider the in-rack liquid-to-air unit for retrofits into existing air-cooled halls and liquid-to-liquid units for new halls with facility water.
- Capacity data is for the N+1 pump state, so do not count the higher all-pumps capacity as redundancy margin.
- In the electrical scheme, separate single-phase 100-240 VAC, 48 VDC and three-phase 380-480 VAC supplies by unit.
- Compare filter fineness (25 or 50 micron TCS) with the cold plate requirement.
- At commissioning, test the TCS loop and CDU pressure drop with the rack emulator.
Who should read it
Mechanical and electrical designers and system integrators selecting in-rack or in-row CDUs.
Document contents
- Overview of Boyd liquid cooling solutions
- In-Rack CDUs: Liquid-to-Air performance specifications
- In-Rack CDUs: Liquid-to-Liquid performance specifications
- In-Row CDUs: Liquid-to-Liquid performance specifications
- Boyd's Complete Liquid Cooling EcoSystem for Data Centers
Related standards
- OCP Advanced Cooling Facilities guidance
Publication details
- Authors
- Boyd Corporation
- Publisher
- Boyd
- Year
- 2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Vendor technical literature; no open licence stated
Citation
Boyd Corporation (2026). Liquid-to-Liquid and Liquid-to-Air Coolant Distribution Units for High Performance Data Centers (CDU Comparison). Boyd. https://info.boydcorp.com/hubfs/Thermal/Liquid-Cooling/CDU-Comparison.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.