BullSequana SH Series Powered by Intel Xeon 6 Processors

Bull

Bull's BullSequana SH Xeon 6 document lists four modular scale-up server models from 2U to 19U; published maximum weights are 40, 80, 160 and 415 kg, with 1+1 redundant 2200 or 3000 W PSUs per two-socket module.

On this page

Overview

BullSequana SH is a scale-up x86 server series built on Intel Xeon 6 processors for in-memory computing and critical applications. The series has four models assembled from one to eight two-socket server modules, each 2U high: SH21 (2 CPUs, up to 8 TB DRAM, up to 2 GPUs), SH41 (4 CPUs, 16 TB, 4 GPUs), SH81 (up to 8 CPUs, 32 TB, 8 GPUs) and SH161 (up to 16 CPUs, 64 TB, 16 GPUs in the overview and up to 32 GPUs in the spec table). Modules connect directly up to 8 sockets, and through node controllers in a 3U UBox beyond that.

For facility planning, the physical and electrical tables are the most useful part. Chassis heights for SH21, SH41, SH81 and SH161 are 2U, 4U, 8U and 19U respectively. Published maximum weights are 40, 80, 160 and 415 kg, with a depth of up to 855 mm. Each two-socket module has two hot-swap PSUs in 1+1 redundancy, with 2200 or 3000 W output depending on configuration and 80 PLUS Titanium (up to 96% efficiency). These are PSU output ratings, not measured whole-system input values.

Operating conditions are 10-35 °C ambient air (20 °C/hour gradient), 20-60% non-condensing relative humidity and elevation from sea level to 2500 m. Each module has 12 hot-swap fans (N+1). The document also describes optional direct liquid cooling (DLC), with up to 97% heat dispersion efficiency and operation at a 40 °C inlet water temperature. The document is a manufacturer specification sheet. Rack planning should follow the model, module count and PSU configuration, and PSU output ratings should not stand in for consumption.

Key points

  1. Four models: SH21 (2U), SH41 (4U), SH81 (8U) and SH161 (19U), with up to 2, 4, 8 and 16 CPUs respectively.
  2. Published maximum weights are 40, 80, 160 and 415 kg; dimensions are up to 447 mm (19 in) wide and 855 mm deep.
  3. Each two-socket module has 2 hot-swap PSUs in 1+1 redundancy; output is 2200 W or 3000 W depending on configuration, 80 PLUS Titanium, up to 96% efficiency.
  4. PSU output ratings are not measured whole-system input power.
  5. DRAM reaches 8 TB on SH21, 16 TB on SH41, 32 TB on SH81 and 64 TB on SH161 (with 256 GB DIMMs).
  6. Each module has 12 hot-swap fans in N+1 redundancy.
  7. Operating: 10-35 °C ambient, 20-60% humidity (non-condensing), elevation below 2500 m.
  8. Optional DLC: up to 97% heat dispersion efficiency, operating at a 40 °C inlet water temperature.
  9. PSU cable type is C19-C20, 20 A; voltage 100-120 V / 200-240 V, 50-60 Hz.
  10. UBox: 3U, 2 PSUs in 1+1 (2200 W), 35.5 kg.

Using it in design

  • In rack planning, take height (2U, 4U, 8U or 19U) and published maximum weight (40, 80, 160 or 415 kg) per model; check rack and floor loading for the 415 kg SH161.
  • Build the power budget on two PSUs per two-socket module in 1+1 redundancy; the 2200 or 3000 W PSU output is not consumption, so obtain actual input power per configuration from the manufacturer.
  • Plan C19-C20 20 A cables and 200-240 V circuits for supply.
  • Constrain hall conditions to 10-35 °C and 20-60% relative humidity.
  • If DLC is used, check the 40 °C inlet water assumption against the cooling water design.

Who should read it

Rack, power and cooling designers placing large scale-up servers for in-memory and AI workloads.

Document contents

  1. Series overview
  2. A powerful and scalable range
  3. UBox technical specifications
  4. BullSequana SH21, SH41 and SH81 technical specifications
  5. BullSequana SH161 technical specifications

Publication details

Authors
Bull
Publisher
Bull
Year
2026
Document number
Bull-CS-FS-BullSequana-SH-Xenon6-RGB-v3
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Bull (2026). BullSequana SH Series Powered by Intel Xeon 6 Processors. Bull. Bull-CS-FS-BullSequana-SH-Xenon6-RGB-v3. https://www.bull.com/hubfs/Documents/Bull-FS-BullSequana-SH-Xeon6.pdf?hsLang=en

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.