Ultrastar Data102 Installation Guide, Revision 05
Western Digital
Western Digital's installation guide for the 4U, 102-drive Ultrastar Data102 JBOD enclosure: 1181-1197 mm rack depth, 118.8 kg loaded mass, ~1300 W typical and 1600/1800 W maximum PSU output.
On this page
Overview
The document is Western Digital's Revision 05 installation guide, dated March 2026, for the Ultrastar Data102, a high-density 4U storage enclosure that hosts up to 102 SAS or SATA hard drives. With 26 TB Ultrastar HC580 drives the maximum capacity is stated as 2.65 PB. The guide covers product description, environmental, electrical and mechanical specifications, rack requirements, compatible drives, regulatory compliance, safety, packaging and installation steps.
On the rack side the guide sets a precise geometry: 1181-1197 mm of usable depth between rack frames, vertical rail spacing of 812.8-914.4 mm, a minimum 450 mm width and the EIA-310 hole pattern. The rack must offer a static load rating of at least 1360.7 kg and a dynamic rating of 1020.5 kg. In service position the enclosure extends about 950 mm, so rack stabilisers are required against tipping.
The electrical section has to be read with care. The stated maximum (1600 W Delta, 1800 W Artesyn PSU) and typical (~1300 W) values are PSU output power to the system; input power drawn from the supply varies with efficiency and load sharing. The PSUs are 80 PLUS Platinum with C14 connectors. On a low-line (110-127 VAC) feed the PSUs power up but the drives do not, and the enclosure stays in low-power mode.
For environment, the operating range is 5-35 °C, 8-90% non-condensing relative humidity and an altitude of -300 to 3048 m, with 1 °C of derating per 300 m above 900 m. The guide is a product installation document: it gives no facility heat load, airflow or row-layout figures, which the designer must derive.
Key points
- 4U enclosure with up to 102 SAS/SATA drives; 2.65 PB maximum capacity with 26 TB HC580 drives.
- Typical power ~1300 W, maximum 1600 W (Delta PSU) or 1800 W (Artesyn PSU); these are PSU output values, and input power depends on efficiency.
- Usable rack depth 1181-1197 mm, vertical rail spacing 812.8-914.4 mm.
- Inputs of 200-240 VAC (high line) and 110-127 VAC (low line); drives do not run on low line.
- Redundant PSUs are 80 PLUS Platinum; AC inrush per PSU is at most 40 A peak.
- Loaded mass 118.8 kg (dual IOM, 102 drives; excludes CMA and accessories).
- Rack static load 1360.7 kg, dynamic load 1020.5 kg; the enclosure extends ~950 mm in service position.
- Operating environment 5-35 °C, 8-90% RH, up to 3048 m; 1 °C per 300 m derating above 900 m.
- Installation and removal need two people; 1219.2 mm of front clearance for install and 1371 mm for removal.
Using it in design
- When choosing the rack, check that usable depth is 1181-1197 mm and rail spacing 812.8-914.4 mm, and that the cable management arm length is 1148 or 1183 mm.
- In facility power calculations treat 1600/1800 W as PSU output; correct the grid input with PSU efficiency and load sharing, and check the single-feed redundant PSU case separately.
- Verify floor loading and rack load class against the 118.8 kg loaded mass per enclosure; decide on bottom-of-rack placement from centre-of-gravity considerations.
- In cooling design hold the 35 °C upper limit and a maximum 20 °C per hour temperature change; apply derating above 900 m at high-altitude sites.
- Carry the ~950 mm service extension and the 1219-1371 mm front clearance into aisle width.
Who should read it
Data-centre mechanical and electrical designers placing storage enclosures in racks, and field installation teams.
Document contents
- Overview
- Disclaimers
- Safety
- Packaging
- Installation
Publication details
- Authors
- Western Digital
- Publisher
- Western Digital
- Year
- 2026
- Document number
- D018-000236-000 Rev05
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Western Digital (2026). Ultrastar Data102 Installation Guide, Revision 05. Western Digital. D018-000236-000 Rev05. https://documents.westerndigital.com/content/dam/doc-library/en_us/assets/public/western-digital/product/platforms/ultrastar-data102-hybrid-platform/installation-guide-ultrastar-data102.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
