CNDCP Comments on the Draft EU Data Centre Sustainability Rating Scheme

Original title Comments on the Draft EU Data Centre Sustainability Rating Scheme (CNDCP Recommendations on the Draft Delegated Act, April 2026)

Climate Neutral Data Centre Pact (CNDCP) · Climate Neutral Data Centre Pact

In April 2026 the Climate Neutral Data Centre Pact asked the Commission to build climate normalisation, aggregated scoring and a simple REF into the draft EU rating scheme so warm-region sites are not penalised.

On this page

Overview

This five-page submission from the Climate Neutral Data Centre Pact (CNDCP) responds to the Commission's draft Delegated Regulation. The Pact, founded in 2021, brings together enterprise, colocation and cloud operators and aims for climate-neutral operation by 2030. It welcomes the draft as a transparency step, praising the priority on PUE, WUE and REF, removal of data-traffic KPIs and reuse of existing reporting frameworks.

The main criticism concerns methodology. Cooling degree days (CDD) appear only as context and play no role in assigning PUE and WUE classes. A facility with identical design and operation therefore ranks lower in a warm region, and the rating reflects geography rather than performance. CNDCP proposes a few CDD-based climate zones with adjusted thresholds, with measured values reported transparently and normalised classes calculated centrally.

Other recommendations: aggregate classes into one comparable score, developed with industry through the 2029 review; use a more non-linear PUE scale and reconsider very low thresholds such as 1.1; and widen WUE classes to fit different cooling technologies. Waste-heat-reuse readiness should be defined by in-boundary provisions such as offtake valves and heat-exchanger space, without requiring heat pumps or network equipment.

Finally, REF should remain a simple metric under CEN/CENELEC EN 50600, independent of procurement method. Guarantee-of-origin conditions such as 15-minute temporal matching, geographic limits and asset-age caps diverge from the RED III framework and apply only to data centres, so they should be recognised voluntarily. The paper notes the scheme will underpin Minimum Performance Standards expected in 2027.

Key points

  1. The draft prioritises PUE, WUE and REF and drops data-traffic KPIs.
  2. CDD is informational only and does not influence PUE/WUE class assignment, creating structural bias.
  3. CNDCP proposes a limited number of CDD-based climate zones with adjusted thresholds.
  4. Classes and raw data are not aggregated into a single score; methodology should be developed with industry through the 2029 review.
  5. PUE thresholds such as 1.1 should be reconsidered and the scale made non-linear.
  6. Waste-heat readiness should mean offtake valves and heat-exchanger space; mandating heat pumps risks embedded carbon and stranded assets.
  7. REF should follow EN 50600 and stay independent of procurement; 15-minute matching should be voluntary.
  8. The rating will be the basis for Minimum Performance Standards expected in 2027.

Using it in design

  • When setting a design PUE target, assess climate zone (CDD) and the class the site would be reported under; model the effect in warm climates.
  • Weigh WUE against PUE in cooling selection by climate, and document the class effect of water-based cooling.
  • Reserve offtake-valve points and heat-exchanger space for waste-heat readiness; tie heat pump installation to actual demand.
  • Build the REF calculation to the EN 50600 definition and track guarantee-of-origin evidence separately.
  • Define the site boundary for rating data, with metering points, from the start.

Who should read it

Engineers, sustainability managers and policy teams designing or operating data centres in the EU.

Document contents

  1. Executive Summary
  2. Broad Observations
  3. Methodology for Classes
  4. Climate Normalization
  5. Waste Heat Reuse Definition and DC Boundary
  6. REF Calculation Methodology
  7. Guarantee of Origin

Related standards

  • Delegated Regulation (EU) 2024/1364
  • Directive (EU) 2023/1791
  • ISO/IEC 30134-2
  • ISO/IEC 30134-9

Publication details

Authors
Climate Neutral Data Centre Pact
Publisher
Climate Neutral Data Centre Pact (CNDCP)
Year
2026
Document language
English
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No open licence stated.

Citation

Climate Neutral Data Centre Pact (2026). Comments on the Draft EU Data Centre Sustainability Rating Scheme (CNDCP Recommendations on the Draft Delegated Act, April 2026). Climate Neutral Data Centre Pact (CNDCP). https://www.climateneutraldatacentre.net/wp-content/uploads/2026/05/CNDCP-Recommendations-on-the-Draft-Delegated-Act-on-EU-Data-Centre-Rating-Scheme-April-2026.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.