Lightning and Surge Protection Concept for Data Centres

DEHN

A 2022 DEHN white paper that plans, as one concept, risk assessment, external lightning protection, earthing, shielding and bonding network, lightning protection zones and surge protective device (SPD) stages for data centres, based on EN 50600 and EN 62305.

On this page

Overview

The paper stresses that lightning and surges are often overlooked risks that can cause fires, outages and data loss, so protection should be planned early; retrofitting is usually difficult and costly. EN 50600-2-2 (power supply and distribution) requires lightning protection and refers to the EN 62305 series; EN 50174-2/-3, IEC 60364-4-44 and 5-53, EN 61000-4-9/-10 and EN 50310 are also relevant.

The planning flow starts with the EN 62305-2 risk analysis: the structure is assessed, risk RX is compared with tolerable risk RT, measures are chosen if it is exceeded, and the lightning protection level (LPL) and LPS class follow. For a data centre this is usually LPS class I, maximum effectiveness. If a law or regulation specifies a class, no risk analysis is needed. The external LPS has air-termination, down conductors, earthing, separation distance and lightning equipotential bonding.

Cooling towers, chillers and PV modules on the roof make it hard to keep separation distances with conventional air-termination rods. The paper's answers are to use reinforcement as a natural conductor with a 5 m x 5 m mesh connected every metre to form equipotential surfaces (spreading impulse currents of up to 200 kA, 10/350 microsecond, over many parallel paths), and to use HVI insulated conductors. A common, global earthing system is preferred.

Internally, the zone concept LPZ 0A, 0B, 1 and 2...n applies. At the 0A/0B to 1 boundary, lightning-current-carrying type 1 arresters sit in the low-voltage main distribution board; type 2 arresters sit at boundaries 0B-1 and above and 1-2 and above, and type 3 at end devices, coordinated per EN 62305-4. Table 1 recommends type 2 arresters with nominal discharge current of 20 kA per pole at LPL I, 15 kA at LPL II and 10 kA at LPL III-IV (8/20 microsecond). Measures for sub-distribution boards, server rooms and technical building equipment are also listed.

Key points

  1. EN 50600-2-2 requires lightning protection per the EN 62305 series; typical LPS class for a data centre is I.
  2. The risk analysis (EN 62305-2) compares RX with RT; the result sets LPL and LPS class.
  3. Impulse currents can reach 200 kA (10/350 microsecond) and must be spread over many parallel paths.
  4. Equipotential surfaces use a 5 m x 5 m reinforcement mesh with connections every 1 m.
  5. HVI conductors solve the separation distance problem where roofs are dense with structures; a common global earthing system is preferred.
  6. Type 1 SPDs at the LPZ 0A/0B-1 boundary, type 2 at 0B-1 and above and 1-2 and above, type 3 at end devices.
  7. Type 2 SPD recommendation: LPL I 20 kA, LPL II 15 kA, LPL III-IV 10 kA (8/20 microsecond, per pole).
  8. Shielding of cables and rooms is combined with the equipotential bonding network in server rooms.
  9. Earthing is hard to correct afterwards; EN 62305-3 and EN 50310 requirements apply.

Using it in design

  • Commission the lightning risk analysis (EN 62305-2) at the start of building design and reflect the LPS class in the power distribution scheme.
  • Resolve air-termination and separation distance together with cooling equipment and PV on the roof layout; provide HVI conductors if needed.
  • Connect reinforcement and metal elements to a 5 m x 5 m equipotential network and plan a common earthing system.
  • Set SPD stages (type 1, 2, 3) at zone boundaries on incoming and distribution levels and verify coordination.
  • Check SPD nominal discharge current against LPL (20, 15, 10 kA).

Who should read it

Data-centre electrical and earthing designers, lightning protection specialists and project managers.

Document contents

  1. Lightning and surge protection measures: an essential component in the safety concept
  2. Normative requirements
  3. Risk assessment
  4. Lightning protection system
  5. Earthing system
  6. Shielding and equipotential bonding network
  7. Lightning protection zone concept
  8. Low-voltage main distribution board
  9. Sub-distribution board
  10. Server rooms
  11. Technical building equipment

Publication details

Authors
DEHN
Publisher
DEHN
Year
2022
Document number
WPX050/EN/0422
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public manufacturer document or page inspected. No document-specific redistribution permission established; retain metadata and original short summaries only.

Citation

DEHN (2022). Lightning and Surge Protection Concept for Data Centres. DEHN. WPX050/EN/0422. https://www.dehn-international.com/sites/default/files/media/files/data-centres-wpx050-en_1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.