Navigating the Liquid Cooling Landscape for AI Data Centers in 2026 and Beyond: A Practical Guide for European Businesses

Original title Navigating the liquid cooling landscape for AI data centers in 2026 and beyond: A practical guide for European businesses

Delta Electronics

Delta Electronics' 2026 white paper sets out how European AI data centres choose between air, RDHx, direct-to-chip, immersion and two-phase cooling by rack density (30, 80, 160 kW thresholds), and between retrofit and new-build paths.

On this page

Overview

The white paper opens with rack power rising from about 3 kW three years ago to 130 kW-class GPU racks today (GB200 and GB300 systems with 72 GPUs) and projections of 1 MW toward 2027. It stresses that permitting for 50-100 MW facilities can take up to five years in Europe, that infrastructure decisions can be outdated in under 12 months, and that the economic measure of an AI facility is cost per token.

Two paths are defined: a time-to-market approach retrofitting existing licensed facilities with liquid-to-air (L2A) cooling to earn revenue within 9-12 months, and a future-proof approach building new purpose-designed facilities with liquid-to-liquid (L2L) infrastructure ready for 800 V DC distribution. The decision framework rests on three questions: heat load per rack, new build or retrofit, and constraints on water, ESG and operational skills.

Technology thresholds are given: air or RDHx up to about 30 kW; air-assisted liquid cooling for 30-160 kW; direct-to-chip above that; immersion above 80 kW where hardware can be standardised; and two-phase as a planning option. The paper also covers electrical integration, CDU hydraulics and control, leak and condensation management, TCO and waste-heat revenue. It is a vendor white paper; product data are Delta's GoCool range.

Key points

  1. Typical racks were about 3 kW three years ago; GB200 and GB300 systems put 72 GPUs in a 130 kW rack; next-generation levels of 144 kW to 600 kW per rack are cited.
  2. Thresholds: air or RDHx to about 30 kW, air-assisted liquid cooling 30-160 kW, direct-to-chip above; immersion considered above 80 kW with standard hardware.
  3. RDHx is suggested as a starting point for moderately dense racks up to about 50 kW.
  4. GoCool-225 L2A CDU supports up to 225 kW per rack, needs no raised floor or facility piping, and includes 50 micron integrated filtration (25 micron optional).
  5. GoCool-3000 L2L CDU gives 3,000 kW (at 1.0 kW/LPM), 4°C ATD and 334 kPa external pressure drop; it targets racks above 100 kW and 40-60°C output water.
  6. A 100 kW rack needs about five times the power feed of a conventional 20 kW rack; 800 V HVDC reduces the roughly 1% loss at each AC/DC conversion.
  7. L2A is advised for retrofit and L2L for new build; recovered heat can be sold to networks such as district heating.
  8. The EU EED requires PUE, WUE and ERF reporting; the paper cites thresholds of 500 kW IT power and 1 MW rated power in different places.

Using it in design

  • Establish heat load per rack and map the cooling architecture to the thresholds: below 30 kW air or RDHx, 30-160 kW air-assisted liquid, above that direct-to-chip; consider immersion only with standard hardware.
  • For retrofit capacity consider L2A CDUs that need no facility chilled water; for new build plan L2L together with a waste-heat output temperature target.
  • Specify CDU filter fineness (50 or 25 micron) for cold plate microchannels, and verify temperature and pressure requirements (30-35 PSI or 80-90 PSI) in pump selection.
  • On the power side recompute per-rack feed, busway and PDU sizes, and leave room for 800 V DC distribution in new builds.
  • Include leak detection zoning, CDU response logic (reduce flow, alarm, shut down a zone) and control that keeps supply water above dew point.
  • Run the TCO study over a 10-year horizon and use liquid cooling telemetry for EED reporting.

Who should read it

Operators planning AI data-centre investment in Europe, consulting engineers and infrastructure decision makers.

Document contents

  1. Introduction
  2. What is driving the need for liquid cooling?
  3. The AI/HPC thermal inflection point in Europe
  4. Assessing readiness
  5. Technology selection (decision framework, where each technology fits, Delta's portfolio)
  6. Design and implementation (power and electrical integration, thermal and hydraulic design, materials and fluids, space planning)
  7. Phased deployment
  8. Operations (operational risk, cybersecurity)
  9. Business case (TCO, compliance, monetizing waste heat)
  10. Reference architectures and engagement approach

Publication details

Authors
Delta Electronics
Publisher
Delta Electronics
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer source inspected. No document-specific redistribution permission established. Metadata and original brief summaries only; local downloads are research evidence, not a redistribution package.

Citation

Delta Electronics Navigating the liquid cooling landscape for AI data centers in 2026 and beyond: A practical guide for European businesses. Delta Electronics. https://besmart.delta-emea.com/assets/2026-09-28_Delta-AI-infrastructure-liquid_cooling_Ai_datacenters-CKuSMu40.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.