D-Link 5000 Series Data Center Switches Hardware Installation Guide, Version 1.20

Original title 5000 Series Data Center Switches Hardware Installation Guide v1.20

D-Link

D-Link's guide for the 1U DXS-5000-54S, DQS-5000-32S, DQS-5000-32Q28 and DQS-5000-54SQ28 data centre switches: 295-420 W maximum power, 0-45 °C, 1+1 redundant PSUs and 4 fans.

On this page

Overview

The document is version 1.20 of D-Link's hardware installation guide for the 5000 Series data centre switches. Four models are covered: DXS-5000-54S (48 x 10G SFP+ and 6 x 40G QSFP+), DQS-5000-32S (32 x 40G QSFP+), DQS-5000-32Q28 (32 x 100G QSFP28) and DQS-5000-54SQ28 (48 x 25G SFP28 and 6 x 100G QSFP28). The switches are described as deployable as top-of-rack (ToR), end-of-row (EoR) or leaf. The guide covers safety warnings, hardware description, installation, connections, management, technical specifications and cables.

Physical installation uses standard 19-inch, 1U rack brackets. Each switch has two preinstalled AC or DC power modules (1+1 redundant) and four fan modules. Fan and power modules come in separate front-to-back or back-to-front airflow versions; the guide stresses that the airflow direction of power and fan modules must match, and that a wrong airflow configuration can cause overheating. Green-labelled PSUs are used for port-side exhaust and blue-labelled PSUs for port-side intake.

The technical specification table gives maximum power as 295, 406, 420 and 395 W by model and maximum heat dissipation as 1006.58, 1385.27, 1433.04 and 1347.74 BTU/hr. Dimensions are 440 x 406 x 44 mm, weight 8.7-9 kg, operating temperature 0-45 °C, relative humidity 5-95% non-condensing and acoustic level up to 74 dB. Input is 100-240 V AC, 50/60 Hz.

The safety section asks for loading the rack from the bottom up, keeping total rack load within 80% of the branch circuit rating, and grounding the chassis to the rack frame. The guide is a product installation document; it gives no facility heat load calculation or rack density plan.

Key points

  1. Four models: DXS-5000-54S (48 x 10G + 6 x 40G), DQS-5000-32S (32 x 40G), DQS-5000-32Q28 (32 x 100G), DQS-5000-54SQ28 (48 x 25G + 6 x 100G).
  2. Maximum power: 295 W, 406 W, 420 W and 395 W; maximum heat dissipation: 1006.58, 1385.27, 1433.04 and 1347.74 BTU/hr.
  3. 1U, 440 x 406 x 44 mm; weight 9 kg (8.7 kg for DQS-5000-32Q28).
  4. Operating 0-45 °C, 5-95% RH (non-condensing); storage -40 to 70 °C.
  5. 1+1 redundant PSUs, input 100-240 V AC, 50/60 Hz; DXS-PWR550AC 550 W AC and DXS-PWR800DC 800 W DC modules.
  6. Four fans; front-to-back or back-to-front airflow; power and fan module airflow direction must match.
  7. Acoustics: maximum 69.8-74 dB, minimum 57.2-62 dB.
  8. Total rack load must not exceed 80% of the branch circuit rating.

Using it in design

  • In rack power and heat budgets use 295-420 W and 1006-1433 BTU/hr per model; plan two feeds (A/B) because of the 1+1 PSU structure.
  • Match the airflow direction (port-side intake or exhaust) to cold and hot aisle orientation; verify the label colour or direction of PSU and fan modules.
  • Keep room temperature within the 0-45 °C operating limit and leave airflow clearance around the switch.
  • In circuit protection sizing limit rack load to 80% of the branch rating.
  • Write bottom-up loading with the heaviest item first into site instructions and check chassis grounding.

Who should read it

Data-centre network, electrical and mechanical designers and field engineers installing ToR, EoR or leaf switches.

Document contents

  1. Safety Instructions
  2. Introduction
  3. Hardware Description (Power and Fan Modules)
  4. Hardware Installation (Rack Mounting, Power and Fan Modules, Grounding)
  5. Switch Connections
  6. Switch Management (D-Link OS, ONIE)
  7. Appendix A: Technical Specifications
  8. Appendix B: Cables and Connectors
  9. Regulatory Statements

Publication details

Authors
D-Link
Publisher
D-Link
Year
2020
Document number
v1.20
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

D-Link (2020). 5000 Series Data Center Switches Hardware Installation Guide v1.20. D-Link. v1.20. https://ftp.dlink.ru/pub/Switch/DQS-5000-32S/Description/5000_Series_A1_Hardware_Installation_Guide_v1.20%28WW%29.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.