WaveStar STS 250-1600 A guide specification
Eaton / Power Distribution Inc.
A guide specification, Revision 001 of 5 May 2017, from Power Distribution, Inc. (PDI, an Eaton business) that sets out procurement requirements for the WaveStar static transfer switch (STS) from 250 to 1600 A. Automatic transfer, including sense time, completes within 1/4 cycle; standard short-circuit withstand is 22 kAIC, with 65 or 100 kAIC optional.
On this page
Overview
This is a 22-page guide specification written so that a data-centre designer can lift it into a tender package, organised in three parts: General, Product and Execution. The device is a three-pole, two-position static transfer switch that moves a load automatically or manually between two three-phase AC sources of the same nominal voltage, phase rotation and frequency. Every transfer is break-before-make; the two sources are never connected together, and transfers are required to stay within CBEMA limits.
Current ratings are 250, 400, 600, 800, 1000, 1200 and 1600 A and voltages are 208, 400, 480 and 600 V; the unit carries 100% load continuously. The operator chooses between two algorithms. The POG algorithm transfers within 1/4 cycle including sense time for in-phase conditions. The PDI-patented VSS algorithm lengthens the transfer to roughly 1/2 cycle and at most 3/4 cycle, and in return balances the volt-seconds of a magnetic load so that transformer inrush stays below twice the STS rated current. Manual transfers take no more than 1/8 cycle between in-phase sources.
The reliability section sets an MTBF target above 2,000,000 hours and the redundancy that supports it: triple-redundant logic with voting, a backup logic board independent of the main one, redundant signal buses, two independent gate drivers per source and triple-redundant logic power supplies. The SCRs must be puck type, rated 2,880 A RMS continuous on 250-800 A units and 7,060 A on 1000-1600 A units. Short-circuit withstand is achieved to UL 1008S without SCR protective fusing.
Three operating modes are defined: Normal, Bypass and Redundant. Retransfer to the preferred source is configurable, with a delay between 4 seconds and 10 minutes. The phase window for manual transfers defaults to ±20 degrees and can be widened to 180 degrees. Transfers are inhibited when load current exceeds about three times the full-load rating, so a load-side fault is not carried to the second source. Maintenance bypass is manual, uses Kirk key interlocks, and is transparent to the load on the same source.
The specification also fixes physical and environmental limits: NEMA 1 enclosure, 0 to 40 °C operating temperature, no derating up to 5000 feet and 6% derating per 1000 feet above that. Cabinet dimensions, weights and service and ventilation clearances are listed by current rating. Modbus RTU, Modbus TCP/IP and SNMP v1 are supported for monitoring without add-in cards. As a manufacturer's specification its values are specific to the WaveStar product, and equivalence has to be assessed separately when other vendors' offers are compared against these clauses.
Key points
- Current ratings 250, 400, 600, 800, 1000, 1200 and 1600 A; voltages 208, 400, 480 or 600 V three-phase, 3-wire plus ground; 50 or 60 Hz.
- Sense and transfer time: 1/4 cycle or less with the POG algorithm; about 1/2 to a maximum of 3/4 cycle with the VSS controlled-inrush algorithm.
- Overload capability: 100% continuous, 125% for 30 minutes, 150% for 2 minutes, 300% for 30 seconds, 500% for 10 seconds.
- Short-circuit withstand at 600 V or below is 22 kAIC standard, with 65 kAIC and 100 kAIC optional.
- Accepts ±10% source voltage and up to 15% THD, load power factor from 0.5 to 1.0 leading or lagging, and load crest factor up to 3.5.
- MTBF target exceeds 2,000,000 hours; logic, signal buses, gate drivers and power supplies are redundant.
- Cabinet dimensions (depth x width x height): 32.75 x 36.50 x 74.75 in for 250-600 A; 32.75 x 48.00 x 74.75 in for 800 A; 43.00 x 84.00 x 74.75 in for 1000-1200 A; 43.00 x 84.00 x 89.25 in for 1600 A.
- Approximate weights: 900 lb for 250-600 A, 1,100 lb for 800 A, 3,600 lb for 1000-1200 A, 4,000 lb for 1600 A.
- Cooling: 250 and 400 A units are fanless convection cooled; 600 and 800 A units have 3 active plus 3 reserve fans; 1000-1600 A units have 6 active plus 3 reserve fans.
- Clearances: 36 in at the front plus 36 in at the right side (250-800 A) or rear (1000-1600 A) for service; 6 in on all sides and 18 in above for ventilation.
Using it in design
- Calculate the prospective fault current at the STS; if it exceeds 22 kA, write the 65 or 100 kAIC option into the specification.
- Where transformer-based PDUs sit downstream, base the design on the VSS algorithm and a transfer of up to 3/4 cycle, and confirm with the CBEMA/ITIC curve that the IT load tolerates it.
- Reserve footprint and service clearance by current rating: front and right-side access up to 800 A, front and rear access at 1000 A and above.
- On sites above 5000 feet (about 1500 m), apply the 6% current derating per 1000 feet.
- Decide the retransfer setting (Yes/No) and its delay of 4 seconds to 10 minutes together with the UPS and generator scenarios.
- In protection coordination, note that the STS inputs are by default MCSWs with no thermal element; assign overload protection to the upstream breaker.
Who should read it
Electrical engineers designing dual-fed distribution, teams writing STS specifications and comparing bids, and designers responsible for protection coordination.
Document contents
- 1 General: Summary, Standards, Definitions, System Description, Documentation, Warranty, Quality Assurance, Submittal Requirements
- 2.1 Electrical Requirements
- 2.2 Environmental Specifications
- 2.3 Components: Enclosure
- 2.4 STS Cooling
- 2.5 STS Access
- 2.6 Electrical Construction
- 2.7 Static Transfer Switch Module Design
- 2.8 Redundancy
- 2.9 STS Operation
- 2.10 Operator Interface
- 2.11 Operator Screens
- 2.12 Alarms
- 2.13 Networking
- 2.14 Current Transformers
- 2.15 Contractor Boards
- 2.16 Web Pages
- 3 Execution: Packing and Shipping, Factory Testing, Factory Witness Test, Certified Test Report, Installation, Start-Up
Publication details
- Authors
- Eaton / Power Distribution Inc.
- Publisher
- Eaton / Power Distribution Inc.
- Year
- 2017
- Document number
- Revision 001
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Eaton / Power Distribution Inc. (2017). WaveStar STS 250-1600 A guide specification. Eaton / Power Distribution Inc.. Revision 001. https://www.eaton.com/content/dam/eaton/products/backup-power-ups-surge-it-power-distribution/power-distribution-for-it-equipment/pdi-static-transfer-switch/WaveStar-STS-Guide-Specification-250A-1600A.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.