Grid Accommodation of Dynamic HPC Demand (EE HPC State of the Practice Workshop, 2019)

Energy Efficient HPC Working Group · Grant L. Stewart, Gregory A. Koenig et al.

A workshop paper from the EE HPC WG explaining why rapid power swings from large supercomputers can disturb voltage on the local grid and what can mitigate them.

On this page

Overview

This document is a paper from the Energy Efficient HPC Working Group (EE HPC WG) for its State of the Practice Workshop in Kyoto in 2019; the authors are Grant L. Stewart, Gregory A. Koenig, Jingjing Liu, Anders Clausen, Sonja Klingert and Natalie Bates. It explains why rapid power swings from large supercomputers can disturb voltage on the local grid and what can mitigate them.

The paper reviews the basics of voltage fluctuation, reactance and grid stiffness, lists stabilising devices, and presents four anonymised HPC site case studies built from questionnaires and interviews. The sites differ in transmission voltage, nearby generation and VAR support. Stabilising devices include generators with automatic voltage regulation, capacitor banks, SVCs and STATCOMs. The scale is notable: exascale systems are expected to have 30-40 MW peak demand and up to 20 MW load swings in 15 ms (one 60 Hz cycle) to several seconds. One cited deployment saw 1.9 MW fluctuations causing 9% voltage fluctuation during initial testing; another study measured about 0.4% for 1.5 MW, anticipating up to 4%. ORNL's Summit has a 13 MW peak demand.

The case-study sites range from a developing site (1.3 MW peak with 1.0 MW swings, planning 14 MW) to sites on 345 kV and 500 kV networks with heavy VAR support. The authors conclude that dynamic-load modelling with the utility is needed early in planning, because mitigation measures can be comparable in cost to the computing system itself. These figures show that the effect depends on the grid's strength at the point of connection as much as on the size of the swing.

Key points

  1. Exascale systems are expected to have 30-40 MW peak demand and up to 20 MW load swings in 15 ms (one 60 Hz cycle) to several seconds.
  2. One deployment saw 1.9 MW fluctuations causing 9% voltage fluctuation during initial testing; another study measured about 0.4% for 1.5 MW, anticipating up to 4%.
  3. ORNL's Summit has a 13 MW peak demand.
  4. Mitigating devices: generators with automatic voltage regulation, capacitor banks, SVCs and STATCOMs.
  5. Case-study sites range from a developing site (1.3 MW peak, 1.0 MW swings, planning 14 MW) to sites on 345 kV and 500 kV networks with heavy VAR support.
  6. Mitigation can be comparable in cost to the computing system itself, so early planning with the utility is needed.
  7. Related standard: IEEE 1453 (voltage fluctuations/flicker).

Using it in design

  • Site/grid-connection screens should capture expected load-step magnitude and ramp time and short-circuit strength at the point of connection.
  • Warn when large fast load swings are planned on a weak grid without VAR compensation or energy-storage buffering.
  • Do dynamic-load modelling with the utility at the start of planning.
  • Add the cost of stabilising devices (SVC, STATCOM, capacitor banks) to the project budget early.

Who should read it

Electrical designers and grid-connection engineers planning sites with large, fast-changing HPC and AI loads.

Related standards

  • IEEE 1453 (voltage fluctuations/flicker)

Publication details

Authors
Grant L. Stewart; Gregory A. Koenig; Jingjing Liu; Anders Clausen; Sonja Klingert; Natalie Bates
Publisher
Energy Efficient HPC Working Group
Year
2019
Document number
EE HPC SOP Workshop, Kyoto, 2019
Event
EE HPC State of the Practice Workshop 2019, Kyoto
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Grant L. Stewart; Gregory A. Koenig; Jingjing Liu; Anders Clausen; Sonja Klingert; Natalie Bates (2019). Grid Accommodation of Dynamic HPC Demand (EE HPC State of the Practice Workshop, 2019). Energy Efficient HPC Working Group. EE HPC SOP Workshop, Kyoto, 2019. EE HPC State of the Practice Workshop 2019, Kyoto. https://datacenters.lbl.gov/sites/default/files/Grid%20Accommodation%20of%20Dynamic%20HPC%20Demand%20%281%29.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.