Diesel Generator Maintenance and User Manual (EMSA)
Original title Dizel Jeneratör Bakım ve Kullanım El Kılavuzu
EMSA Jeneratör
EMSA Jeneratör's manual sets 1 m clearance around and 2 m above the set, air openings of at least 1.5 times the radiator area and a maximum 3% voltage drop on the power line.
On this page
Overview
The manual brings safety, siting, installation, fuel system, battery care, electrical connections, panel operation, maintenance and troubleshooting for EMSA Jeneratör sets into one document. The manufacturer states that the sets are built to the TS ISO 8528 series, and the document notes a declared service life of 10 years for generators.
The siting section covers location, sound and vibration isolation, concrete plinth, combustion air, cooling and ventilation, exhaust and fuel system. It asks for at least 1 m clearance around the set and 2 m above, a level load-bearing floor, protection from harmful dust and vapours, and an access path for bringing the set into the room. The plinth is 200-300 mm high, extends more than 250 mm around the set and is designed under the civil engineer's responsibility.
For ventilation, air should enter the room at the alternator side, pass over the engine and through the radiator, and leave through a flexible canvas bellows duct. Inlet and outlet windows should by rough calculation be at least 1.5 times the radiator area, and louvres in front of sound barriers must give at least 50% free air passage. Movable louvres are preferred in cold climates and can open and close automatically with engine operation.
The electrical section takes ambient temperature, installation method and run length into account in cable selection; voltage drop on the power line must not exceed 3%. The document is a manufacturer's manual and does not replace an independent design standard, but it gives concrete, field-oriented rules for room dimensions, fuel tank and pipework arrangement.
Key points
- At least 1 m is left around the set and at least 2 m above it for service and cooling.
- Air inlet and outlet windows are at least 1.5 times the radiator area; louvres before sound barriers give at least 50% free area.
- Sound level at 1 m from the sound barriers is targeted at 85 dBA; thicker barriers give further reduction.
- The concrete plinth is 200-300 mm high with more than 250 mm margin around the set, raised where water may collect.
- Exhaust back pressure must not exceed the engine maker's limit; each bend has a radius of at least 1.5 times the pipe inside diameter, and the pipe can be enlarged by 1 inch every 6 m or 3 bends.
- Each generator has its own exhaust system; exhausts of several sets must not be joined into one pipe.
- Fuel tanks are not filled completely; 10% of capacity is left for expansion in heat. Fuel sulphur must not exceed 0.5% by volume and water and sediment 0.05%.
- Voltage drop on the power line must not exceed 3%, and load imbalance between phases must stay within 15%.
- Coolant uses roughly a 50% antifreeze and 50% water mix.
Using it in design
- Verify 1 m clearance around and 2 m above the set and the delivery route into the room on the layout drawings.
- Pre-size air openings at 1.5 times the radiator area and louvre free area at 50%; tie automatic louvres to the generator start signal.
- Calculate exhaust back pressure against the engine maker's limit, with a separate run and flexible connection for each set.
- For long runs from generator to distribution board, check cable size for voltage drop at starting current as well.
- Place the day tank in the generator room and choose the main-to-day tank connecting pipe no smaller than the day tank feed pipe.
Who should read it
Engineers designing generator rooms and fuel systems, and installation and operations teams.
Document contents
- Introduction and Set Label
- Safety and Health
- Lifting, Siting, Installation and Storage
- Choosing the Generator Location
- Sound and Vibration Isolation
- Concrete Plinth
- Cooling and Ventilation
- Exhaust
- Fuel System
- Oil and Antifreeze
- Batteries
- Electrical Connections
- Maintenance and Troubleshooting
Publication details
- Authors
- EMSA Jeneratör
- Publisher
- EMSA Jeneratör
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.
Citation
EMSA Jeneratör Dizel Jeneratör Bakım ve Kullanım El Kılavuzu. EMSA Jeneratör. https://emsa.gen.tr/images/manual/manual-tr.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.