Technical guideFree to readYear not stated

Wastewater and Drainage Pumps Installation Guide

Original title Atıksu ve Drenaj Pompaları Montaj Kılavuzu

ETNA

ETNA installation guide for wastewater and drainage pumps: guided-rail and fixed installation diagrams, ball-type check valve on the discharge line, two-float control panel for run and alarm levels, and Hazen-Williams pipe loss tables.

On this page

Overview

ETNA's short installation guide covers pumps designed to remove wastewater and drainage water containing solids in residential and industrial buildings. Septic pumps sit in a pit at the lowest level of the building, or in a lidded fibreglass collection box, and transfer the water to the sewer network. On macerating models a cutter in the suction line breaks up solids so the pump does not clog.

The installation section makes three main recommendations. A guide-rail (slide) system is preferred for maintenance, because the pump can be lowered and lifted along guide pipes without emptying the pit. The discharge line gets a full-bore ball-type check valve, which stops water in the line returning to the pit when the pump stops. Third, a protection and control panel with thermal overload protection guards the windings against overcurrent.

The panel can take two float switches. The first manages the operating level: the pump starts when the pit fills to the set level and stops when it drops to the minimum. The second is set slightly above the maximum operating level and signals an alarm horn if the pump fails to run, warning of overflow risk. At commissioning the motor rotation is checked against the arrow before the pump goes into the pit, and both floats are adjusted.

The last pages give Hazen-Williams (UNI 9489) friction loss tables for new galvanised steel pipe, covering flows of 10 l/min (0.6 m³/h) to 1750 l/min (105 m³/h) and pipe sizes from 1/2 inch to 6 inch. The document is a roughly three-page installation note; it contains no hydraulic selection method or flood scenario.

Key points

  1. A ball-type check valve is mandatory on the discharge line; it is full-bore and the ball prevents backflow toward the pump.
  2. A guide-rail system is recommended: the pump can be removed along the rails without draining the chamber.
  3. Two installation layouts are shown: guided fixed installation for EFP30/EFP30D, and fixed installation with a conical union for EFP30T/EFP30V.
  4. The first float runs and stops the pump by level; the second sits slightly above the operating level and raises an alarm if the pump does not run.
  5. The panel's thermal protection switch guards against winding burn-out from overcurrent.
  6. At commissioning, motor rotation is verified against the arrow before lowering the pump; if the pit is empty and the pump is being placed, the main switch is opened to prevent dry running.
  7. Pressure loss tables use the Hazen-Williams formula for flows of 10-1750 l/min and 1/2 to 6 inch galvanised steel pipe.
  8. Macerating septic pumps break up solids with a cutter at the suction inlet.

Using it in design

  • Provide guided-rail installation in basement, generator and pump-room drainage pits so a failed pump can be replaced without emptying the pit.
  • Fit a check valve on every pump discharge line and keep it accessible for maintenance.
  • In the drainage panel, plan a separate high-level alarm float in addition to the operating float, and connect the alarm to the BMS or monitoring system.
  • When sizing discharge pipe and lift, use the document's loss table or your own hydraulic calculation; the table holds values for new galvanised steel pipe only.
  • Write motor rotation check, both float settings and the dry-running precaution into the commissioning checklist.

Who should read it

Mechanical engineers designing data-centre basement and site drainage, and installation and commissioning teams.

Document contents

  1. Use
  2. Points to note during installation
  3. Points to note during commissioning
  4. Wastewater and drainage pump connection diagrams
  5. Straight pipe pressure loss table

Publication details

Authors
ETNA
Publisher
ETNA
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official publisher material inspected. No document-specific commercial redistribution permission established; retain metadata and original short summaries only.

Citation

ETNA Atıksu ve Drenaj Pompaları Montaj Kılavuzu. ETNA. https://www.etna.com.tr/uploads/source/Montaj%20K%C4%B1lavuzlar%C4%B1/etna_atiksu_drenaj_pompasi_kullanimklavuzu.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.