Intel's Open IP Immersion Cooling Reference Solutions, Single Phase, 2U and 4U AAIC User Guide
Original title Intel’s Open IP Immersion Cooling Reference Solutions: Single Phase: 2U and 4U AAIC User Guide, Revision 1.0
Intel
Intel's February 2024 user guide (document 816305) describes the 3/7 kW air-assisted single-phase 2U/4U AAIC immersion tank that integrates tank, CDU and monitoring system.
On this page
Overview
The guide introduces the 2U and 4U Air Assisted Immersion Cooling (AAIC) systems from Intel's Open IP immersion cooling reference solutions. AAIC is a stand-alone system designed for easy deployment, especially in harsh environments; the 3 kW (2U) and 7 kW (4U) cooling capacities share the same uniform flow field design and modular scalability. The document states it covers products in the design phase and that designs should not be finalised from it.
The system has three parts: a stainless steel tank with anti-rust and anti-corrosion protection and a flip-up top cover that can be sealed against coolant evaporation, a CDU integrated into the tank, and a monitoring system. Cooled coolant enters at the tank bottom through the CDU pump, takes heat from high-TDP server components, rises by thermal buoyancy, and is drawn from the top by the CDU pump to a fan-cooled radiator. The monitoring system offers manual and automatic operation modes.
The guide covers key parts and dimensions, 1U and 2U server chassis dimensions (with and without ears, slide thickness), installation precautions (at least 2000 mm wide by 2100 mm long and at least 1800 mm height to open the cover), the monitoring interface (home, menu, manual mode, settings, pump outlet pressure setting, trend chart, messages, error codes, defaults) and troubleshooting (coolant level and temperature sensor alarms, sensor replacement, coolant recycle and refill, top cover sealant strip and cable gland replacement).
Key points
- Document 816305, Revision 1.0, February 2024.
- 2U AAIC is rated 3 kW and 4U AAIC 7 kW cooling capacity.
- Tank, CDU and monitoring system are integrated in one unit.
- The tank is stainless steel; the flip-up cover can be sealed to prevent coolant evaporation.
- Cooled coolant enters at the bottom, rises by thermal buoyancy and is drawn from the top to a fan-cooled radiator.
- Installation space is at least 2000 mm (W) by 2100 mm (L) with at least 1800 mm height to open the cover.
- The monitoring system provides manual and automatic operation modes.
- Troubleshooting covers level sensor alarm, temperature sensor, coolant recycle and refill, and sealant and cable gland replacement.
- 1U and 2U server chassis dimensions are given.
Using it in design
- For edge or lab installations, put at least 2000 x 2100 mm floor area and 1800 mm ceiling height into the layout plan for the 2U/4U AAIC.
- Limit IT load to the 3 kW (2U) or 7 kW (4U) capacity and set overload margin.
- Check server chassis dimensions and slide thickness for fit inside the tank.
- Add level and temperature sensor alarms to the BMS monitoring list.
- Write keeping the cover closed and replacing the sealant strip into the maintenance plan; it limits coolant evaporation.
- The guide covers design-phase products; verify final design decisions with the current Intel document.
Who should read it
Engineers installing or evaluating immersion cooling in edge and lab environments and operations teams.
Document contents
- 2U/4U AAIC brief
- 2U/4U AAIC overview
- Server chassis dimensions
- 2U/4U AAIC installation
- Monitoring system instruction
- Common troubleshooting
Publication details
- Authors
- Intel
- Publisher
- Intel
- Year
- 2024
- Document number
- 816305 Revision 1.0
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Intel (2024). Intel’s Open IP Immersion Cooling Reference Solutions: Single Phase: 2U and 4U AAIC User Guide, Revision 1.0. Intel. 816305 Revision 1.0. https://cdrdv2-public.intel.com/816305/816305_Intel%20Open%20IP%20Immersion%20Cooling%20Reference%20Solutions%20-Single%20Phase-%20User%20Guide%202U_4U%20AAIC_Rev_1_0.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.