Pressure Drop Analysis of Direct Liquid Cooled (DLC) Rack (ITherm 2017)

IEEE · Sami Alkharabsheh, Bharath Ramakrishnan et al.

This ITherm paper measures and models flow and pressure distribution in a commercial direct-liquid-cooled rack.

This document is sold by IEEE and is available from the publisher’s site. SoSo CAD does not sell or distribute it; this page holds only catalogue details and our own summary.

On this page

Overview

This record consists only of the metadata (abstract) of a paper presented at IEEE ITherm 2017 (DOI 10.1109/ITHERM.2017.7992570) by Sami Alkharabsheh, Bharath Ramakrishnan and Bahgat Sammakia; the full text has not been read. The paper measures and models flow and pressure distribution in a commercial direct-liquid-cooled rack comprising a coolant distribution module, supply/return manifolds and server cold-plate modules. The authors built pressure-flow curves for each component and an experimentally validated flow network model.

The model errors are 2.5% for server-module flow and 3.8% for coolant distribution module flow. This shows that the validated flow network model predicts flows within a few percent. According to the results, server modules account for 56% of total rack pressure drop. Of the server-module pressure drop, 69% comes from plumbing (corrugated hoses, quick disconnects, fittings) rather than the cold plate.

The measured flow maldistribution among servers was attributed to variation in micro-channel cold-plate manufacturing. The study was carried out on a single commercial rack architecture, so the percentages are specific to that rack and cannot be generalised to every system. Because the record relies only on the abstract, details of the method and operating conditions are not given here.

Key points

  1. Flow network model errors: 2.5% for server-module flow and 3.8% for coolant distribution module flow.
  2. Server modules account for 56% of total rack pressure drop.
  3. 69% of server-module pressure drop comes from plumbing (corrugated hoses, quick disconnects, fittings) rather than the cold plate.
  4. Measured flow maldistribution among servers was attributed to micro-channel cold-plate manufacturing variation.
  5. Pressure-flow curves were built for each component, with an experimentally validated flow network model.
  6. The study rests on a single commercial rack; values cannot be generalised.
  7. The record rests only on the abstract; the full text was not read.

Using it in design

  • Include cold-plate, hose, quick-disconnect and fitting pressure losses in rack-level hydraulic calculations.
  • Treat a flow network solver as accurate enough for design-stage flow balancing.
  • Allow for server-to-server flow maldistribution in the design margin.
  • Assess quick disconnects and hose selection for their effect on total pressure drop.
  • Verify the values for your own rack architecture against manufacturer data.

Who should read it

Mechanical engineers and thermal analysts designing direct-liquid-cooled rack and manifold hydraulics.

Publication details

Authors
Sami Alkharabsheh; Bharath Ramakrishnan; Bahgat Sammakia
Publisher
IEEE
Year
2017
Document number
DOI 10.1109/ITHERM.2017.7992570
Event
IEEE ITherm 2017
Document language
English
Source type
Standard
Access
Paid; available from the publisher
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Sami Alkharabsheh; Bharath Ramakrishnan; Bahgat Sammakia (2017). Pressure Drop Analysis of Direct Liquid Cooled (DLC) Rack (ITherm 2017). IEEE. DOI 10.1109/ITHERM.2017.7992570. IEEE ITherm 2017. https://par.nsf.gov/biblio/10058219

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.