A Computational Fluid Dynamic Investigation of a Data Centre Employing Rear Door Heat Exchangers

Journal of Engineering Technology and Applied Sciences · Michael Busby, David Green et al.

A 2022 paper by Northumbria and Cambridge researchers that uses CFD and field measurements to study a hall with 77 rear door heat exchanger racks and 3 uncooled racks.

On this page

Overview

The paper models a data hall cooled by active rear door heat exchangers (RDHX) at server, rack and room scale. The hall holds seventy-seven cooled racks and three uncooled racks added later in the middle of the room. The central question is how those uncooled racks change temperature distribution in the hall, which is held at roughly 25-26 °C ambient.

The method has three steps. A 320 W rack server (Dell PowerEdge 1750) is first simulated at idle, medium, high and very high load for inlet temperatures from 24 to 28 °C in 2 °C steps, with heat sources set to constant surface temperatures. Those results are then combined with measured temperature and velocity fields to build four room scenarios (B to E). The water circuit and RDHX fans are not modelled in detail; rack outlet boundaries are represented by measured values.

At server level, heat dissipation is directly tied to the velocity profile inside the server. At room level, the rear of highly loaded racks raises the front-of-rack temperature of the racks opposite. Clusters of three or more highly loaded racks have a clearly larger effect than a single highly loaded rack, whose exhaust diffuses faster.

Modelling error for the uncooled racks is large: average error is 15.08, 26.24, 26.56 and 26.54 percent for scenarios B, C, D and E. Measured temperatures range from 25.32 to 42.25 °C while the models give about 36 °C at those points. Results are specific to this layout and these model assumptions, but they give useful direction when reviewing existing designs.

Key points

  1. The hall has 77 rear door heat exchanger racks and 3 uncooled racks, with ambient temperature of 25-26 °C.
  2. The server model is 320 W, 44.7 x 68.3 x 4.2 cm, with inlet temperature swept from 24 to 28 °C in 2 °C steps.
  3. CPU heatsink surface temperatures are 40 °C (medium), 60 °C (high) and 75 °C (very high); inlet velocity is 0.25 m/s at idle and 0.50 m/s at medium load.
  4. Heat dissipation in the server is directly related to its internal velocity profile; a break in the fan arrangement can leave one heatsink area under-cooled.
  5. Clusters of three or more highly loaded racks affect the opposite front-of-rack temperature more than an isolated highly loaded rack.
  6. Highly loaded, high-velocity racks placed strategically can reduce the effect of hot air from uncooled racks.
  7. Modelling error for uncooled racks ranges from 15.08 to 26.56 percent; measured temperatures span 25.32-42.25 °C.
  8. With all racks at maximum load, large areas of the hall may reach temperatures up to 31 °C.

Using it in design

  • In an RDHX hall, control clustering of high-load racks rather than scattering them blindly; assess the effect of groups of three or more on the opposite row's inlet temperature.
  • If uncooled racks must exist, place them near highly loaded, high-velocity racks so the hot exhaust is diluted.
  • Feed CFD rack outlet boundaries with measured temperature and fan speed data, and include the tendency to under-predict uncooled racks in the error margin.
  • For a design holding ambient at 25-26 °C, add local zones up to 31 °C to the full-load check list.
  • Track later-added uncooled racks as a separate thermal risk item and verify their placement by field measurement.

Who should read it

Mechanical engineers designing rear door or hybrid cooled halls, and analysts using CFD for room-level temperature distribution.

Document contents

  1. Introduction
  2. Materials and methods (server model, rack model, room scenarios)
  3. Field measurements
  4. Results and discussion (room and row monitoring comparisons)
  5. Conclusion

Publication details

Authors
Michael Busby; David Green; Madeleine Combrinck
Publisher
Journal of Engineering Technology and Applied Sciences
Year
2022
Document number
10.30931/jetas.950046
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Michael Busby; David Green; Madeleine Combrinck (2022). A Computational Fluid Dynamic Investigation of a Data Centre Employing Rear Door Heat Exchangers. Journal of Engineering Technology and Applied Sciences. 10.30931/jetas.950046. https://dergipark.org.tr/en/download/article-file/1815118

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.