Seismic Vibration Control of a Data Center Building Considering Fragility Curves of Accommodated Computer Servers
The Japan Society of Mechanical Engineers / NCTAM · Takanori Ito, Masayuki Kohiyama
A 2013 NCTAM conference paper from Keio University: in a 15-storey data-centre model, the 30-year server damage probability falls from 93.1% to 84.9% when active-control parameters are tuned.
On this page
Overview
The paper treats equipment malfunction as one of the serious seismic damages to a building and takes data-centre servers as the example. A 15-storey data-centre building is represented as a mass-spring model. Servers sit on seismic isolation floors at the 2nd and 15th storeys, and an active vibration controller is mounted on the top floor. The building's fundamental period is 2.25 s, the isolation floor's is 4 s, and damping is 0.01 for the building and 0.20 for the floor.
The control force is determined by linear quadratic regulator (LQR) theory, with a maximum force of 500 kN. The cost function weights three quantities: building absolute acceleration, inter-storey drift, and isolation floor displacement relative to the floor. Damage thresholds are 2.0 m/s2 for server absolute acceleration, 0.1 m for server deformation and 0.25 m for isolation floor displacement. Input is 150 scaled waves representing the rare earthquake defined in the Japanese building code notification.
A fragility curve gives damage probability against ground-motion intensity (peak ground velocity, PGV). Combining it with a 30-year exceedance hazard curve yields the probability P that servers are damaged in the next 30 years. The study uses hazard data for the Hiyoshi site in Yokohama. P becomes the criterion for choosing control parameters.
In the uncontrolled building, P for servers on the 15th floor is 93.1%. The main cause of damage is the isolation floor exceeding its movable range; server deformation never caused damage. A parameter sweep reduces P to 84.9% with the best combination, about 8.2 points lower. A notable finding is that when the control-input cost is small, a large weight on inter-storey drift lowers P the most. The study is a fundamental method proposal and does not rely on measured fleet failure rates.
Key points
- Model: 15-storey data centre, servers on isolation floors at the 2nd and 15th storeys, active controller on the top floor (up to 500 kN).
- Building fundamental period 2.25 s, damping 0.01; isolation floor period 4 s, damping 0.20; server mass 400 kg.
- Damage thresholds: server absolute acceleration 2.0 m/s2, server deformation 0.1 m, isolation floor displacement 0.25 m; exceeding any one counts as damage.
- Input: 150 scaled waves matching the code's rare-earthquake definition; peak ground velocity (PGV) is the intensity measure.
- In the uncontrolled building, the 30-year damage probability for 15th-floor servers is 93.1%.
- The best parameter combination from the sweep lowers damage probability to 84.9% (about 8.2 points reduction).
- Damage is dominated by the isolation floor exceeding its displacement limit; server deformation caused no damage in the analysis.
- When the control-input cost drops to 1.0 x 10^-10 or lower, a large weight on limiting inter-storey drift lowers damage probability the most.
Using it in design
- Check the stroke of server-room isolation floors against displacement demand in the design earthquake, not only acceleration; in this study displacement was the governing quantity.
- Compare equipment damage by a 30-year damage probability that combines fragility and hazard curves, not by a single design earthquake.
- Assess server platforms on upper floors against higher floor acceleration and drift demands than lower floors.
- If active or semi-active control is considered, tune maximum force and weighting parameters against site-specific hazard data to minimise damage probability.
- Use the paper's damage thresholds (2.0 m/s2 acceleration, 0.25 m floor displacement) as a starting point for comparison and replace them with your own equipment test data.
Who should read it
Structural engineers designing data-centre buildings and isolated server floors in seismic regions, and researchers studying equipment fragility.
Document contents
- Research Background and Objective
- Analysis Model and Outline
- Analysis Results and Discussion
- Conclusion
Publication details
- Authors
- Takanori Ito; Masayuki Kohiyama
- Publisher
- The Japan Society of Mechanical Engineers / NCTAM
- Year
- 2013
- Document number
- 62nd NCTAM; GS04-03
- Document language
- Japanese
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public English abstract and Japanese PDF opened; © 2013 JSME. PDF downloaded and extracted. No open redistribution licence found.
Citation
Takanori Ito; Masayuki Kohiyama (2013). Seismic Vibration Control of a Data Center Building Considering Fragility Curves of Accommodated Computer Servers. The Japan Society of Mechanical Engineers / NCTAM. 62nd NCTAM; GS04-03. https://doi.org/10.11345/japannctam.62.0.60.0
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.