Data Centre Standard (ICTA.2.2.002:2023)

Original title Data Centre Standard

ICT Authority Kenya

Kenya ICT Authority's third-edition government data centre standard (effective 1 July 2023) requires at least Tier 2 for public data, 1.2 m cold and 1.0 m hot aisles, and UPS batteries sized for at least 8 hours.

On this page

Overview

ICTA.2.2.002:2023 is the third edition of the Kenya ICT Authority's standard for government data centres (MCDAs); approved 3 May 2023, effective 1 July 2023, with review after three years. It covers site selection, design, layout, cabling, environment, physical security, information security, infrastructure, operations, and maintenance and service-level agreements.

The site and design section requires Ministry of ICT approval of projects, at least Tier 2 for data centres holding public data, a feasibility study and a site selection checklist. Protection against floods, lightning, earthquake and fire is expected; the building must not be in an airport flight path, at least 0.8 km from a railroad or major highway, and at least 0.4 km from an airport, research lab, chemical plant, landfill, river, coastline or dam.

Technical requirements are specific: cold aisle at least 1.2 m and hot aisle at least 1.0 m; front clearance at least 1 m (1.2 m preferred) and rear clearance at least 0.6 m (1 m preferred); 24/7/365 HVAC on backup generator; generator and UPS mandatory with batteries supporting the centre for at least 8 hours; fire separation of at least 1 hour, NFPA-75 compliance and pre-action sprinklers in computer rooms; backbone cabling of at least 24-core 50 micron fibre.

It is a compliance standard rather than a design guide; many numeric design parameters (cooling capacity, efficiency) are left to manufacturers and the Tier level. Appendix I defines Tier 1-4 redundancy and Appendix II gives the site selection checklist. Suppliers must provide a service level agreement with at least 99.99% availability.

Key points

  1. Every data centre holding public data must be at least Tier 2; every centre must fall within the Tier 1-4 classification.
  2. Cold aisle at least 1.2 m, hot aisle at least 1.0 m; front clearance at least 1 m (1.2 m preferred), rear at least 0.6 m (1 m preferred).
  3. Every data centre has generator and UPS; batteries must support the centre for at least 8 hours; distribution through PDUs.
  4. A dedicated 24/7/365 HVAC system with automatic dampers on backup generator is required; cabinets form hot and cold aisles; blanking panels in unused spaces and perforated floor tiles in cold aisles.
  5. Site distances: at least 0.8 km from a railroad or major highway; at least 0.4 km from an airport, research lab, chemical plant, landfill, river, coastline or dam.
  6. Fire: separated from other occupancies by at least 1-hour fire-rated construction; NFPA-75; pre-action sprinklers and water drainage in the computer room.
  7. Cabling: laser-optimised 50 micron fibre backbone of at least 24 cores; power and communication on separate pathways or a physical barrier; 300 mm minimum access headroom between trays.
  8. Floor and heights: raised floor minimum 18 inches; racks preferably no taller than 2.1 m with 2.4 m as the cabinet upper limit.
  9. Supplier SLAs guarantee at least 99.99% data-centre service availability; a single entry point, intruder detection and CCTV are required.

Using it in design

  • Target at least Tier 2 redundancy for public data and show N+1 component redundancy on the power and cooling single-line drawings.
  • Verify 1.2 m cold aisle, 1.0 m hot aisle and front/rear service clearances on the layout plan.
  • Size UPS battery autonomy to the 8-hour requirement; include generator-backed HVAC and sprinkler drainage in the design.
  • Add flight path, the 0.8 km and 0.4 km distances, and flood, lightning and earthquake risk to the site checklist.
  • Plan separate pathways for power and data; specify the 24-core 50 micron fibre backbone and a labelling scheme.

Who should read it

Engineers and contractors designing or auditing Kenyan government data centres, and policy teams preparing a similar national standard.

Document contents

  1. Introduction
  2. Scope
  3. Application
  4. Normative references
  5. Definitions
  6. Abbreviations
  7. Data center site selection, design and planning
  8. Planning layout: cooling, power, fire detection and suppression
  9. Cabling infrastructure
  10. Environment
  11. Physical security
  12. Information security
  13. Data center infrastructure
  14. Data center operations
  15. Maintenance and SLAs
  16. Appendix I: Tiered reliability standard
  17. Appendix II: Site selection checklist

Publication details

Authors
ICT Authority Kenya
Publisher
ICT Authority Kenya
Year
2023
Document number
ICTA.2.2.002:2023
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public official source inspected; no document-specific commercial redistribution permission established. Original short summaries and metadata only; downloads are local research evidence. PDF p. 2 expressly reserves ICTA copyright and reproduction rights.

Citation

ICT Authority Kenya (2023). Data Centre Standard. ICT Authority Kenya. ICTA.2.2.002:2023. https://cms.icta.go.ke/sites/default/files/2023-07/Data%20Center%20Standard-Third%20Edition%202023.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.