Technical guideFree to readYear not stated

Cybersecurity Framework 5.0 Implementation Guide: SF.1 Physical Access Controls

Original title Guía de implementación del Marco de ciberseguridad 5.0: SF.1: controles de acceso físico

Agencia de Gobierno Electrónico y Sociedad de la Información y del Conocimiento (Agesic)

Agesic's MCU 5.0 guidance for Uruguay sets four maturity levels (13 controls) of physical access control for data centres, including no windows on outer walls, visitor logging with purpose, and an audit evidence list.

On this page

Overview

Requirement SF.1 asks organisations to implement physical access controls for the facilities and equipment in data centres and related areas, with the aim of reducing unauthorised access, theft, damage and misuse. Controls are spread across four levels. Level 1 covers identifying areas that need access control, controlling entry to the data-processing facility and managing access authorisations. Level 2 adds security perimeters, other secure areas and an access log.

Level 3 introduces a formally approved physical access control policy and review of access records. Level 4 requires a periodic access review procedure, internal control activities and controls on connection time and conditions for access from external locations. Thirteen controls are listed (SF.1-1 to SF.1-13), and the implementation guide adds concrete expectations on architecture and structure.

On architecture, critical information assets must sit in a structure that withstands the usual Uruguayan weather (rain, storms, strong wind) and is built from non-flammable, non-lightweight materials, with a steel or concrete structural system. The site may not be flood-exposed or in a place whose access can be disrupted by natural or human conditions. A raised technical floor is recommended, the power room should preferably be separate from the computer room, and cameras must record all activity inside.

On access, an autonomous system with card, RFID or biometric readers is required, remotely administered and keeping access history; outer walls have no windows and perimeter security is needed. Cabinets with lockable doors are suggested. The visitor register records the purpose of the visit. For cloud data centres the provider must cover every control and present evidence. Additional notes cover healthcare institutions, including access to medical equipment and a controlled room for mobile medical devices.

Key points

  1. Four levels and 13 controls: SF.1-1 to SF.1-3 (level 1), SF.1-4 to SF.1-7 (level 2), SF.1-8 to SF.1-10 (level 3), SF.1-11 to SF.1-13 (level 4).
  2. A data centre may not be located on a flood-exposed site or where access can be affected by natural or human conditions.
  3. The structural system is steel or concrete; floor, door and masonry materials are non-flammable; a raised technical floor is recommended.
  4. The building is designed for wind loads under applicable codes and the provisions for essential facilities (for example International Building Code Risk Category III).
  5. The power room should be separate from the computer room; electrical installations must be protected against accidental human contact.
  6. An autonomous system with card, RFID or biometric readers, remotely managed and keeping access history, is required; outer walls have no windows.
  7. The visitor register includes the reason for the visit; access logs are reviewed periodically and the review procedure is documented.
  8. Audit evidence: policy, authorisation procedure, list of secure areas and authorised people, access logs for the audit period, procedures for unattended equipment, review procedure and internal control records.

Using it in design

  • Define flood exposure and access-route disruption as screening criteria in site selection, and run the same check on existing buildings.
  • Write no windows on data-hall outer walls, perimeter security, CCTV and card, RFID or biometric access control into the architectural brief.
  • Plan the power room separately from the computer room and add raised flooring and a non-flammable materials list to the specification.
  • Select an access control system that is remotely manageable and keeps history; add a purpose-of-visit field to the visitor register.
  • Design the audit evidence (area-to-authorisation matrix, periodic access review report) as outputs of the operating procedures.

Who should read it

Data-centre security and facility designers, information-security auditors and operators complying with Uruguay's public-sector cybersecurity framework.

Document contents

  1. Requirement and objective
  2. Controls: level 1 to level 4
  3. Implementation guide: architecture and structure, physical access, policy and procedures, physical access log
  4. Sector notes: healthcare institutions, electronic money issuers
  5. Audit evidence guide

Publication details

Authors
Agencia de Gobierno Electrónico y Sociedad de la Información y del Conocimiento (Agesic)
Publisher
Agencia de Gobierno Electrónico y Sociedad de la Información y del Conocimiento (Agesic)
Year
Year not stated
Document number
MCU 5.0, SF.1
Document language
Spanish
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public official source inspected. No document-specific commercial redistribution permission established. Metadata and original brief summaries only; local evidence is not a redistribution package.

Citation

Agencia de Gobierno Electrónico y Sociedad de la Información y del Conocimiento (Agesic) Guía de implementación del Marco de ciberseguridad 5.0: SF.1: controles de acceso físico. Agencia de Gobierno Electrónico y Sociedad de la Información y del Conocimiento (Agesic). MCU 5.0, SF.1. https://www.gub.uy/agencia-gobierno-electronico-sociedad-informacion-conocimiento/comunicacion/publicaciones/guia-implementacion-del-mcu-50/seguridad-fisica-del-ambiente/sf1

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.