Comparative Study on Heat Dissipation Performance of Pure Immersion and Immersion Jet Liquid Cooling System for Single Server
Buildings (MDPI AG) · Linhui Yuan, Yu Wang et al.
A 2024 Buildings (MDPI) study finds an immersion-jet hybrid reaches a surface heat transfer coefficient 2.6 times that of pure immersion on a single-server bench, with correlation error below 18%.
On this page
Overview
The paper notes that server cooling is critical as server counts grow and that immersion-jet technology for large-scale operation remains unexplored. The proposed system combines immersion liquid cooling with jet cooling, directing coolant jets onto hot components, to see whether the combination raises heat dissipation capacity.
A single-server test bench compares pure immersion with the immersion-jet system and examines inlet water temperature, jet distance and inlet flow rate. At steady state the surface heat transfer coefficient of the immersion-jet system is 2.6 times that of pure immersion. Adjusting jet distance and flow rate raised the coefficient by about 475.9 and 1745.0 W/(m² K) respectively.
Dimensional analysis simplifies the system model into a dimensionless relationship covering inlet water temperature, jet distance and inlet velocity, with correlation error below 18%. The work is at single-server scale; moving to tank and facility scale needs separate validation.
Key points
- Steady-state surface heat transfer coefficient of immersion-jet is 2.6 times that of pure immersion.
- Adjusting jet distance raised the coefficient by about 475.9 W/(m² K).
- Adjusting flow rate raised the coefficient by about 1745.0 W/(m² K).
- Variables studied: inlet water temperature, jet distance and inlet flow rate.
- The dimensionless correlation error is below 18%.
- The test was run on a single-server bench.
Using it in design
- Consider jet-assisted flow as an option for local hot spots in immersion tanks.
- Design jet distance and flow rate to be adjustable; most of the gain comes from these two parameters.
- Count jet pump energy against the heat transfer gain.
- Run multi-server validation before carrying single-server results to tank scale.
Who should read it
Thermal engineers designing immersion tanks and server cooling R&D teams.
Publication details
- Authors
- Linhui Yuan; Yu Wang; Risto Kosonen; Zhengchao Yang; Yingying Zhang; Xincheng Wang
- Publisher
- Buildings (MDPI AG)
- Year
- 2024
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Linhui Yuan; Yu Wang; Risto Kosonen; Zhengchao Yang; Yingying Zhang; Xincheng Wang (2024). Comparative Study on Heat Dissipation Performance of Pure Immersion and Immersion Jet Liquid Cooling System for Single Server. Buildings (MDPI AG). https://doi.org/10.3390/buildings14092635
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.