On the Numerical Investigation of Two-Phase Evaporative Spray Cooling Technology for Data Centre Applications

Fluids (MDPI AG) · Ning Gao, Syed Mughees Ali et al.

A 2024 Fluids study models evaporative spray cooling with Lagrangian-Eulerian CFD: air cools by up to 12 °C at high temperature and low humidity, and COP rises from about 90 to 9,500 as droplets shrink from 292 µm to 8 to 15 µm.

On this page

Overview

The study notes that two-phase evaporative spray cooling can significantly cut power use in data centre cooling, but no established method exists for assessing overall performance in terms of the water-energy nexus. To fill this gap a Lagrangian-Eulerian computational fluid dynamics (CFD) model is developed. To represent a modular system, a hollow spray cone nozzle with a Rosin-Rammler droplet size distribution is simulated in a turbulent convective natural-air environment, and the model is validated against experimental data from the literature.

Parametric studies vary domain length, droplet size, water mass flow rate, temperature and humidity. The climate of Dublin, Ireland is used as an example for optimizing the evaporative system, and a new formulation for the coefficient of performance (COP) is established to assess system performance.

Results show a fine-droplet nozzle cuts water consumption (97% in the example) while raising the share evaporated. The findings are numerical; field validation lies outside this summary.

Key points

  1. At elevated temperature and low humidity, evaporation reduces bulk air temperature by up to 12 °C.
  2. Doubling injector water flow raises evaporated mass flow by 188% but lowers evaporation percentage by 28%, reducing COP.
  3. Doubling domain length raises the temperature drop by 175% and relative humidity by 160%, improving COP.
  4. Reducing the Sauter mean diameter from 292 µm to 8 to 15 µm raises system COP from about 90 to 9,500.
  5. Fine droplets reach close to 100% evaporation, versus about 1% for the largest droplet size.
  6. A fine-droplet nozzle reduces water consumption by 97% in the case.

Using it in design

  • When considering evaporative spray cooling, select droplet size and water flow together with temperature and humidity conditions, and quantify the trade-off between water use and cooling effect.
  • A longer air path (domain length) improves cooling effect and COP; leave adequate distance in the layout.
  • Evaporative effect falls as humidity rises; assess against local climate data (Dublin in the example).
  • When carrying CFD results into site design, ask for experimental validation.

Who should read it

Researchers and mechanical designers studying the water and energy performance of evaporative and adiabatic cooling systems.

Publication details

Authors
Ning Gao; Syed Mughees Ali; Tim Persoons
Publisher
Fluids (MDPI AG)
Year
2024
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Ning Gao; Syed Mughees Ali; Tim Persoons (2024). On the Numerical Investigation of Two-Phase Evaporative Spray Cooling Technology for Data Centre Applications. Fluids (MDPI AG). https://doi.org/10.3390/fluids9120284

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.