Performance Analysis of Lake Water Cooling Coupled with a Waste Heat Recovery System in the Data Center
Sustainability (MDPI AG) · Peng Yin, Yang Guo et al.
A 2024 Sustainability study couples lake water free cooling with waste heat recovery: recovery from IT return air gives PUE 1.19 and COP 10.17, and 16 °C water with 20 °C air supply saves up to 26.05%.
On this page
Overview
Data centers need cooling all year and produce a large amount of low-grade waste heat. Free cooling and waste heat recovery are promising ways to cut energy use, but the study notes a significant gap in combining waste heat recovery with lake water cooling. To address it, a system integrating lake water cooling with waste heat recovery is proposed.
To evaluate the energy-saving performance of the system, the influence of heat recovery locations and volumes is investigated, and improvements in system parameters are analyzed. Targeted recovery from sources such as chilled water or air in the server rooms significantly reduces the cooling energy demand.
Recovering heat from the IT equipment return air yields a PUE of 1.19 and COP of 10.17, with cooling system energy consumption reported at 10.06%. Setting chilled water and air supply temperatures to 16 and 20 °C gives potential energy savings of up to 26.05%.
Key points
- The system combines lake water cooling with data center waste heat recovery.
- Recovery location and volume drive energy performance; targeted recovery from server room chilled water or air cuts cooling demand markedly.
- Recovering heat from IT return air gives PUE 1.19 and COP 10.17.
- Cooling system energy consumption is reported at 10.06%.
- Setting chilled water to 16 °C and supply air to 20 °C gives potential savings of up to 26.05%.
Using it in design
- At sites near a lake, river or sea, evaluate free cooling together with waste heat use.
- Fix the heat recovery point (IT return air or chilled water) early; return air recovery gives the best result.
- Assess supply temperatures (chilled water 16 °C, air 20 °C) together with system efficiency and IT temperature limits.
- Results come from simulation; build a model with your own water temperature and flow data.
Who should read it
Mechanical and energy designers studying free cooling from natural water sources with waste heat use.
Publication details
- Authors
- Peng Yin; Yang Guo; Man Zhang; Jiaqiang Wang; Linfeng Zhang; Da Feng; Weike Ding
- Publisher
- Sustainability (MDPI AG)
- Year
- 2024
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Peng Yin; Yang Guo; Man Zhang; Jiaqiang Wang; Linfeng Zhang; Da Feng; Weike Ding (2024). Performance Analysis of Lake Water Cooling Coupled with a Waste Heat Recovery System in the Data Center. Sustainability (MDPI AG). https://doi.org/10.3390/su16156542
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
