The Water Footprint of Data Centers
Sustainability (MDPI AG) · Bora Ristic, Kaveh Madani et al.
An early water-footprint (WF) accounting of data centres from Imperial College London that adds the water embedded in purchased electricity (WFsource) to on-site HVAC water use: indirect (electricity) water normally dominates.
CC BY 4.0: share with attribution
On this page
Overview
As the internet and ICT diffuse rapidly, data-centre energy efficiency has been researched extensively but water footprint has received little to no attention. The paper conducts a preliminary WF accounting for cooling and energy consumption, using an Apple facility dataset and a comparison of HVAC options for a Phoenix data centre. The global data-centre water footprint (HVAC plus energy) is estimated at 767-147,810 million m³ per year, giving a WUEsource of 1047 to 151,061 m³/TJ; this is much higher than the 787 m³/TJ reported by Sharma et al., because WF accounting includes the water embedded in electricity generation.
Outbound data traffic carries a water footprint of 1-205 litres per gigabyte; the high end is close to the 214 L footprint of 1 kg of tomatoes. The indirect water footprint (electricity) is typically much larger than the direct footprint, so the authors say the first priority for cutting data-centre water footprint should be air-side economisation and energy efficiency.
The result is that the HVAC option with the lowest on-site water use is not always the one with the lowest total footprint; the answer flips with the grid's water intensity. Where WFsource is high, HVAC systems that use some water directly can cut the total footprint (Phoenix case); where WFsource is very low, moving away from direct-water HVAC cuts it. The authors name three key uncertainties for data-centre water-footprint work: the water footprint of electricity, psychrometrics (climate) and the water footprint of the HVAC system.
Limits: the authors stress that their global numbers carry very large uncertainty; values are more indicative of the uncertainties involved than a definite quantification. They call for standard WF/WUE reporting.
Key points
- Global data-centre water footprint (HVAC plus energy) is estimated at 767-147,810 million m³ per year, giving a WUEsource of 1047 to 151,061 m³/TJ.
- The WUEsource range is much higher than the 787 m³/TJ reported by Sharma et al., because WF accounting includes the water embedded in electricity generation.
- Outbound data traffic carries a water footprint of 1-205 litres per gigabyte; the high end is close to the 214 L footprint of 1 kg of tomatoes.
- The indirect water footprint (electricity) is typically much larger than the direct footprint, so the first priority should be air-side economisation and energy efficiency.
- Where WFsource is high, HVAC systems that use some water directly can cut the total footprint (Phoenix case); where WFsource is very low, moving away from direct-water HVAC cuts it.
- Three key uncertainties: the water footprint of electricity, psychrometrics (climate) and the water footprint of the HVAC system.
Using it in design
- Compare HVAC options not only by on-site water use but by total water footprint including the grid's water intensity (WUEsource); the ranking can flip with the grid.
- Consider air-side economisation and energy efficiency as the first step to cut water footprint, because electricity-related indirect water usually dominates.
- Report water-footprint results as ranges with the uncertainties of electricity water intensity, climate and HVAC water footprint.
Who should read it
Designers and sustainability managers doing data-centre siting, cooling selection and water-footprint reporting.
Document contents
- 1. Introduction
- 2. Water Footprint for Measuring Water Use Efficiency
- 3. Data Center Structure and Water Footprint of Its Components (3.1 IT Equipment and Uninterruptible Power Supply, 3.2 Direct WF, HVAC, 3.3 Psychrometrics: Temperature and Humidity, 3.4 Indirect WF, Energy Source)
- 4. Uncertainties (4.1 Uncertain WFs of HVAC Systems, 4.2 Water Footprint of Data Centres and Data Centre Outbound Traffic)
- 5. Caveats for Policy and Innovation Recommendations
- 6. Conclusions
Related standards
- ISO/IEC 30134-9 (WUE)
- The Green Grid WP35 (WUE)
Read the document
ristic-water-footprint-data-centers-2015.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Bora Ristic; Kaveh Madani; Zen Makuch
- Publisher
- Sustainability (MDPI AG)
- Year
- 2015
- Volume
- 7
- Issue
- 8
- Pages
- 11260-11284
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
p.1 states the article is open access under the Creative Commons Attribution licence (CC BY 4.0).
Citation
Bora Ristic; Kaveh Madani; Zen Makuch (2015). The Water Footprint of Data Centers. Sustainability (MDPI AG). 7(8), 11260-11284. https://doi.org/10.3390/su70811260
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.