Development of Rolling-Type Parabolic-Surface Floor Isolator (RPFI) and Determination of Mechanical Properties
Middle East Technical University · Cem Eren Aslan
A January 2026 METU master's thesis develops a parabolic-surface rolling floor isolator that reduces seismic acceleration reaching non-structural equipment such as data-centre racks, with reductions up to 90% on some records.
On this page
Overview
Cem Eren Aslan's 132-page master's thesis in Civil Engineering at Middle East Technical University, supervised by Prof. Dr. Uğurhan Akyüz, proposes a new floor isolator to reduce seismic acceleration on non-structural components. In data centres, museums, transmission systems and high-technology facilities, equipment value often exceeds that of the structure, and even base-isolated buildings can show floor accelerations above acceptable limits.
Existing rolling floor isolators in the literature are mostly spherical or conical. This thesis proposes a parabolic surface geometry instead. The equation of motion of a ball rolling on a parabolic surface was derived and solved with the Newmark method under ground motions compatible with a target design spectrum; acceleration reduction and displacement-capacity utilisation ratios were computed for different parabolas and two prototypes were selected.
The two prototypes were manufactured and tested with hysteresis, free vibration, harmonic loading and strong ground motion tests on a single-axis shaking table. Results correlated strongly with the analytical model: at small displacements the parabolic surface behaves like a spherical surface of equivalent radius, and the force-displacement curve can be modelled as bilinear.
The first prototype gave consistent, high acceleration reduction, whereas the second amplified acceleration for some records scaled near its own period. Future work should add multi-axial tests and a damping model specific to parabolic surfaces. The work is mechanical characterisation research, not a product or specification.
Key points
- The proposed RPFI is a rolling floor isolator with a parabolic surface rather than spherical or conical, aimed at non-structural components.
- In experiments the acceleration transmitted to non-structural elements was reduced by up to 90%; this figure arose in the second prototype under GM Set-1 and cannot be used directly to select the final design.
- The second prototype, under GM Set-2 scaled near its fundamental period, did not give the expected reduction and amplified acceleration for some records.
- The first prototype, under GM Set-1 scaled to its dominant period, gave consistent high reduction in agreement with analytical predictions.
- At small displacements the parabolic surface behaves like a spherical one with equivalent radius; hysteresis curves were converted to bilinear models.
- Damping ratio was determined from free vibration tests and depends on the parabola equation; the current calculation adapts the friction-pendulum approach of TEC 2018.
- In harmonic tests the displacement demand rises as the loading frequency approaches the isolator's fundamental period.
- Tests were on a single-axis shaking table only; multi-axial behaviour and large-displacement response are left to future work.
Using it in design
- For base-isolated or multi-storey data centres, consider floor- or rack-level isolation for sensitive equipment on top of building-level isolation.
- Compare the floor isolator's fundamental period with the dominant ground and building periods and check the risk of acceleration amplification under long-period motions.
- Carry the isolator into numerical analyses as an equivalent radius and bilinear model in the small-displacement range.
- In product selection, allow for the limits of single-axis tests and ask for multi-axial verification.
Who should read it
Structural engineers and isolator developers researching seismic protection for data centres and critical facilities.
Document contents
- Introduction
- Definition of parabolic geometry and methodology
- Analytical study
- Experimental study
- Summary and conclusion
Publication details
- Authors
- Cem Eren Aslan
- Publisher
- Middle East Technical University
- Year
- 2026
- Document number
- M.Sc. thesis, Civil Engineering, January 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official publisher or university publicly accessible text; no open redistribution licence established.
Citation
Cem Eren Aslan (2026). Development of Rolling-Type Parabolic-Surface Floor Isolator (RPFI) and Determination of Mechanical Properties. Middle East Technical University. M.Sc. thesis, Civil Engineering, January 2026. https://open.metu.edu.tr/bitstream/handle/11511/118417/10783028.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.