Munters Oasis indirect evaporative cooling
Original title Oasis IEC: Indirect evaporative integrated systems
Munters
Munters Oasis IEC is an indirect evaporative data-centre cooling unit with three operating modes, up to 500 kW per unit and a stated annualised mechanical pPUE of 1.05-1.15.
On this page
Overview
This September 2024 product sheet presents Munters' Oasis indirect evaporative integrated systems. The unit uses the EPX polymer-tube heat exchanger, which can run wet or dry. The elliptical polymer tubes flex slightly in operation and shed mineral scale built up by evaporative cooling. Munters states that the design cuts refrigeration use and installed capacity in most climates.
There are three cooling modes. In Mode 1 the EPX works as a dry air-to-air heat exchanger, with hot data-hall air inside the tubes and ambient air outside. In Mode 2 spray nozzles wet the tube exteriors and scavenger air removes heat by evaporating the water. In Mode 3 supplementary direct expansion (DX) or chilled-water cooling is added after the EPX for extreme conditions.
Four models are listed: Oasis 100, 200, 300 and 400, rated up to 125, 250, 375 and 500 kW, depending on delta T and altitude. Airflow ranges from 10,000-24,000 Sm³/h to 44,000-96,000 Sm³/h. Options cover roof or slab mounting, perimeter mounting, Modbus or BACnet controls and containerised shipping.
The sheet is a short product summary. It gives no climate, water temperature or calculation basis for the annual pPUE range, so the value should be rechecked against project weather data.
Key points
- Up to 500 kW cooling per unit, depending on delta T and altitude.
- Three modes: dry heat exchanger, indirect evaporative (IEC), and IEC with trim DX.
- Annualised mechanical pPUE is stated as 1.05-1.15.
- Four models: Oasis 100/200/300/400 at 125/250/375/500 kW.
- Airflow: 10,000-24,000 Sm³/h for Oasis 100 up to 44,000-96,000 Sm³/h for Oasis 400.
- Oasis 400 measures 592 x 516 x 417 cm with a 30.55 m² footprint.
- Flexing polymer tubes shed mineral scale.
- Options: G4 filter box, mirror access models, Modbus/BACnet, isolation dampers, EC fans, automatic transfer switch.
Using it in design
- Use local dry-bulb and wet-bulb distributions to find the hours in Mode 1, 2 and 3, and recompute the pPUE claim with them.
- Size the trim DX or chilled-water circuit for the load on the hottest humid design day.
- Plan water supply, treatment and drain capacity for evaporative mode separately; the sheet gives no water consumption figure.
- Match roof or perimeter mounting weight, the footprint of up to 30.55 m² and the duct routes with the building design.
- Write the air isolation dampers and the control protocol (Modbus, BACnet) into the BMS scope.
Who should read it
Data-centre mechanical designers comparing air-side and evaporative heat rejection options.
Document contents
- Features
- Options
- Oasis performance table
- Modes
Publication details
- Authors
- Munters
- Publisher
- Munters
- Year
- 2024
- Document number
- OASIS IEC-PS-EN-202409
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Munters (2024). Oasis IEC: Indirect evaporative integrated systems. Munters. OASIS IEC-PS-EN-202409. https://datacenter.munters.com/wp-content/uploads/2026/04/OASIS-IEC-PS-EN-202409.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.