Munters SyCool Split product sheet
Original title SyCool Split 500 kW Product Sheet
Munters
Munters SyCool Split 500 kW is a thermosyphon split-system economizer with no water consumption; nominal effectiveness is 65% and it gives 100% free cooling at 62 °F or lower ambient with 75 °F supply air.
On this page
Overview
This April 2023 product sheet presents the SyCool Split thermosyphon system for new and retrofit projects where a suitable water supply is limited, expensive or unreliable. The system has a nominal 500 kW cooling capacity and two circuits. The evaporator removes room heat by evaporating refrigerant, and the same refrigerant condenses in the condenser to reject heat. Evaporator and condenser can be up to 500 ft apart.
Heat moves passively as long as the condenser sees air cooler than the evaporator. With air delivered to servers at 75 °F and a 20 °F server delta T, 100% free cooling is reached at 75% load when ambient dry bulb is 62 °F or lower. As ambient rises, compressors in the condenser stage in and the system moves from passive to active, without diverting valves. Munters states a nominal thermal effectiveness of 65%.
There are two piping configurations. In A, the 500 kW condenser feeds two 250 kW down-flow evaporators; weights are about 13,000 lb for the condenser and 4,400 lb per evaporator. In B, a single 500 kW fan-array evaporator is used and units can sit side by side with no clearance. Line sizes are 3 or 4 in for vapor and 1.625 or 2 in for liquid.
Performance tables are given at 500 ft elevation, 0.2 in w.c. external static pressure, clean filters and 75 °F supply air. For project-specific performance the sheet refers users to the factory.
Key points
- Nominal cooling capacity 500 kW; two-circuit system.
- No water consumption; the split system removes duct penetrations.
- Nominal thermal effectiveness of 65%.
- With 75 °F supply air and 20 °F delta T at 75% load, 100% free cooling at 62 °F and below.
- Up to 500 ft separation between evaporator and condenser.
- Configuration A: two 250 kW down-flow evaporators, condenser about 13,000 lb.
- Configuration B: one 500 kW fan-array evaporator; side-by-side installation needs no clearance.
- Performance: net room load of 433-530 kW at 103.8-119.7 °F ambient and 19-24 °F delta T.
Using it in design
- On water-constrained sites, compare the no-water thermosyphon with adiabatic and evaporative options on annual water and energy.
- Estimate annual free-cooling hours from the dry-bulb distribution against the 62 °F (about 16.7 °C) threshold for your supply air and server delta T.
- Confirm vapor and liquid line sizes with the manufacturer from vertical and horizontal separation and elbow count.
- At low delta T (19 °F), configuration B drops to 433 kW, so check the design delta T against the table.
- Include the condenser weight (about 13,000 lb) in roof or ground bearing calculations.
Who should read it
Data-centre mechanical designers evaluating air-cooled or thermosyphon economizer options for water-limited sites.
Document contents
- Advantages and operating principle
- Condenser piping configuration A
- Condenser piping configuration B
- Performance tables for A and B
Publication details
- Authors
- Munters
- Publisher
- Munters
- Year
- 2023
- Document number
- SyCool Split 500kW-PS-EN-US-202304
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Munters (2023). SyCool Split 500 kW Product Sheet. Munters. SyCool Split 500kW-PS-EN-US-202304. https://datacenter.munters.com/wp-content/uploads/2026/04/SyCool-Split-500kW-PS-EN-US-202304.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
