Residual Heat from Data Centres (RVO, Netherlands)

Original title Restwarmte datacenters

Netherlands Enterprise Agency (RVO)

The Netherlands Enterprise Agency RVO's data-centre heat-reuse page describes four arrangements with Dutch examples: a local heat-cold ring, direct supply nearby, direct internal use and indirect aquifer-based exchange.

On this page

Overview

The page is guidance published by the Netherlands Enterprise Agency RVO (for the Ministry of Economic Affairs and Climate), with content checked on 31 March 2026. It says more and more data centres seek ways to use the heat they produce, and explains four arrangements with real examples.

The first is connection to a heat-cold infrastructure: data centres join a local lukewarm-water ring, companies on the ring take or supply heat, and aquifer thermal energy storage (WKO) systems absorb peaks. NorthC's installation at the High Tech Campus Eindhoven and the Mijnwater network are examples. The second is Aalsmeer, where a plan moves warm water by open loop to a nearby swimming pool, sports hall, school and grower, with users raising the temperature by heat pump.

The third is Previder's direct internal use in Hengelo: a gas heat pump raises the heat taken from the data centre and the adjoining 12-storey office building needs no extra heating. The fourth is Equinix's indirect exchange in Amsterdam through WKO: the sources are separate but drilled in the same geohydrological strip at 70-180 m depth; the data centre takes cooling from a cold groundwater bubble about 150 m away, and the University of Amsterdam takes the heat.

The page also links to the 'Warmte uit datacenters' (2018) report and a heat opportunity map. The examples are context-specific and carry no numerical capacity or price; read them as installation options, not as a general design rule.

Key points

  1. Four methods: local heat-cold ring, direct supply to the surroundings, direct internal use and indirect use via WKO.
  2. In the ring the data centre joins a lukewarm-water loop; WKO systems absorb peak loads.
  3. Heat exchange takes place at NorthC's High Tech Campus Eindhoven and in the Mijnwater network; the APG head office and a school complex are heated.
  4. In Aalsmeer warm water moves by open loop to a pool, sports hall, school, grower and later homes; users raise temperature with heat pumps.
  5. In Hengelo Previder raises data-centre heat with a gas heat pump; the 12-storey office needs no extra heating.
  6. In Amsterdam Equinix supplies indirect heat and cold to the University of Amsterdam through WKO; the sources are at 70-180 m depth.
  7. Data-centre cooling uses a cold groundwater bubble about 150 m away.
  8. Content was checked on 31 March 2026; Dutch examples cannot be used as general capacity.

Using it in design

  • In site selection, investigate early whether a lukewarm-water ring, district heating network or steady heat users such as a pool or greenhouse exist near the data centre.
  • Match the temperature the user needs (and whether a heat pump must lift it) with the data centre's return water temperature; higher return temperature raises the value of the waste heat.
  • For indirect solutions such as WKO with separate sources, add geohydrological suitability and permit requirements to the project schedule.
  • For internal use, calculate heat-pump placement and the heating load of the adjoining building.
  • For heat sales contracts, consider annual temperature and flow continuity commitments together with cooling redundancy.

Who should read it

Data-centre developers planning heat reuse, planners selecting sites and energy and sustainability managers.

Document contents

  1. Connection to a Heat-Cold Infrastructure
  2. Direct Supply to the Surroundings
  3. Direct Internal Delivery
  4. Indirect Residual Heat Use
  5. Downloads

Publication details

Authors
Netherlands Enterprise Agency (RVO)
Publisher
Netherlands Enterprise Agency (RVO)
Year
Year not stated
Document language
Dutch
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public publisher text inspected. No document-specific commercial redistribution permission established; metadata and original short summaries only.

Citation

Netherlands Enterprise Agency (RVO) Restwarmte datacenters. Netherlands Enterprise Agency (RVO). https://rvo.nl/onderwerpen/energie-besparen-de-industrie/datacenters/restwarmte

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.