Duurzaam koelen van datacenters 2
Netherlands Enterprise Agency (RVO)
RVO's October 2022 brochure describes Dutch practice in free cooling, chilled water, F-gas-free refrigerants and direct liquid cooling through case studies, with PUE of 1.1 and below in several cases.
On this page
Overview
The Netherlands Enterprise Agency RVO published this second edition of its 2012 brochure in October 2022 for the Ministry of Economic Affairs and Climate (author Dr. D.H. Harryvan, Certios B.V.). The introduction shows that electricity delivered to Dutch data centres from the public grid grew from 1,648 GWh (1.48%) in 2017 to 3,178 GWh (2.85%) in 2020. The energy-saving obligation requires every measure with a payback of five years or less. Even today 20-30% of site consumption goes to building facilities, mainly cooling.
After explaining the basics of air cooling (supply air 18-27 °C recommended, at most 35 °C for class 2 equipment; separation of hot and cold air, recirculation and bypass), the brochure covers techniques in turn: direct free cooling and thermal storage, indirect free cooling, F-gases and natural refrigerants, and direct liquid cooling (cold plate and immersion). Each technique gets one or two cases.
Cases: Meta's Luleå site in Sweden reports PUE below 1.1 with direct free air and adiabatic support, but needs large amounts of water in summer. VodafoneZiggo's edge data centres use PCM-assisted direct air cooling for 3-40 kW loads, with average PUE below 1.1 and the cold aisle held at 21-26 °C even when ambient exceeded 35 °C. ECOdc in Sweden uses R1234ze (GWP below 1); Sparkasse Pforzheim runs a 35 kW eChiller with water (R718) as refrigerant to make 20-22 °C chilled water.
The liquid-cooling chapter covers the Kinroy agricultural campus, where 55-60 °C water heats greenhouses without a heat pump, the Bytesnet immersion system supporting up to 60 kW per rack, and Switch Datacenters. The conclusions stress that cooling efficiency alone is not enough and data centres should also contribute to the energy demand of their surroundings. The brochure is a snapshot of the market and not a complete product survey.
Key points
- Grid electricity delivered to Dutch data centres: 1,648 GWh (1.48%) in 2017, 3,178 GWh (2.85%) in 2020.
- Facilities (mostly cooling) still account for 20-30% of site energy.
- Recommended supply air for class 2 IT equipment is 18-27 °C, maximum 35 °C; above 27 °C server fan energy rises quickly.
- Meta Luleå: PUE below 1.1 with direct free air and adiabatic support; summer water use is the drawback.
- VodafoneZiggo PCM-based direct air cooling: 3-40 kW loads, PUE below 1.1; PCM solidifies at 22 °C and melts at 26 °C.
- For modern CRAHs, 20-22 °C chilled water gives 25-27 °C supply air; NorthC Delft PUE below 1.2.
- F-gases warm the climate 124-22,800 times more than CO2; R1234ze has GWP below 1, and the 35 kW eChiller uses water (R718).
- Direct liquid cooling gives 55-60 °C water; an immersion tank holds 24 servers and up to 60 kW; about 15% saving in server energy.
Using it in design
- When pushing supply air to the top of the ASHRAE recommended range (27 °C), calculate the rise in server fan energy above 27 °C together with the cooling saving.
- Write strict hot and cold air separation (aisle containment) into the specification as a precondition for free cooling.
- For direct free cooling, assess summer adiabatic water use and the backup mechanical cooling requirement against the local climate.
- In refrigerant selection, compare F-gas regulation and natural or low-GWP options (R718, R1234ze) with safety and permit limits.
- Integrate waste heat use with liquid cooling that gives 55-60 °C water year-round; note that heat recovery may not pay for small sites without a heat customer.
Who should read it
Data-centre designers, operators and public decision makers evaluating free cooling, waste heat recovery and low-GWP refrigerant options.
Document contents
- Introduction
- Air handling
- Free cooling (direct free air and thermal energy storage)
- Indirect free cooling
- F-gases in chillers
- Direct liquid cooling
- Conclusions
Publication details
- Authors
- Netherlands Enterprise Agency (RVO)
- Publisher
- Netherlands Enterprise Agency (RVO)
- Year
- 2022
- Document language
- Dutch
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official RVO data-centre energy landing opened; linked PDF downloaded/extracted. Colophon copyright RVO October 2022; no explicit reuse licence verified. Link-only.
Citation
Netherlands Enterprise Agency (RVO) (2022). Duurzaam koelen van datacenters 2. Netherlands Enterprise Agency (RVO). https://www.rvo.nl/sites/default/files/2023-02/Duurzaam-koelen-van-datacenters.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
