Energy consumption and economic analysis of air-cooled and immersion liquid-cooled systems for conditioning the white space of a data center
Original title Veri Merkezi Beyaz Alanının Şartlandırılmasında Hava Soğutmalı ve Daldırmayla Sıvı Soğutmalı Sistemlerin Enerji Tüketimi ve Ekonomik Analizi
Yıldız Teknik Üniversitesi · Meltem Ağaoğlu
A 2024 Yıldız Technical University master's thesis calculates that single-phase immersion cooling cuts annual energy by 24% in a 4 MW IT data center in Istanbul but raises the present value of cost by 70% (EUR 3.88 million).
On this page
Overview
Meltem Ağaoğlu's August 2024 master's thesis compares two ways of conditioning a data center white space, air cooling and single-phase immersion liquid cooling, on energy use and economics. It notes that few studies compare single-phase immersion with air cooling. The thesis runs 92 pages; the advisor is Prof. Dr. Derya Burcu Özkan.
The case is a 4,000 kW IT data center near Istanbul Atatürk Airport (2,000 servers of 2 kW each). In the first system servers sit in cabinets, 20 CRAH units supply 22 °C cold air and the room is held at 24 °C. In the second the IT equipment is immersed in dielectric-fluid tanks with 80 tank-embedded CDUs. The air loop is 18/24 °C and the dielectric loop 26/32 °C. Both systems use four free cooling chillers.
With Istanbul's ASHRAE climate data, the liquid-cooled system uses free cooling over a wider outdoor range, so chiller energy falls. Annual cooling system energy is 6.81 GWh (air) and 5.19 GWh (immersion). The economic analysis uses present worth, a 15-year economic life, a 50% discount rate and EUR 0.13/kWh electricity.
Immersion initial investment is EUR 7.96 million versus EUR 3.72 million for air; present worths are EUR 9.43 and 5.55 million. The author judges air cooling the more economical option for this 4 MW case. The result is sensitive to the unit prices assumed and the high discount rate.
Key points
- Case: 4,000 kW IT white space in Istanbul (2,000 servers x 2 kW); 220 cabinets in the air-cooled system, 16 cabinets and 80 immersion tanks in the immersion system.
- Air system: CRAH supply 22 °C and room 24 °C; immersion system: air loop 18/24 °C and dielectric loop 26/32 °C.
- Both systems use 4 free cooling chillers (3 duty + 1 standby); the immersion system uses free cooling over a wider outdoor range.
- Annual cooling system energy: air 6,814,098 kWh, immersion 5,185,454 kWh; immersion is 24% lower.
- Initial investment: air EUR 3,716,080, immersion EUR 7,957,530; annual operating plus maintenance EUR 918,733 and EUR 737,009.
- Assumptions: 15-year life, 50% discount rate, EUR 0.13/kWh, EUR 30,000 heavy chiller maintenance in year 10.
- Present worth of cost: air EUR 5,549,166, immersion EUR 9,428,160; difference EUR 3,878,994.57 (70% higher).
- Conclusion: for the 4 MW IT case the air-cooled system is the more economical choice.
Using it in design
- Compare the energy advantage of liquid cooling (24%) with the initial investment gap (EUR 4.24 million) in one present-worth framework, and run discount rate and electricity price sensitivity separately.
- Account for the warmer 26/32 °C immersion loop raising free cooling hours, and for the separate 18/24 °C loop still needed for air.
- Reflect the white space layout difference (220 cabinets versus 16 cabinets and 80 tanks) in capex and floor area.
- Enter redundancy counts (N+1) for chillers, CDUs, pumps and tanks in the cost table.
- Replace the 2024 Turkish prices and the 50% discount rate with your own project parameters and recompute.
Who should read it
Mechanical designers, consultants and investors in Turkey comparing cooling system options and investment cases for data centers.
Document contents
- Introduction
- Literature review
- Findings and discussion: design conditions
- Air-cooled system (data center design, cooling system and equipment design)
- Single-phase immersion liquid-cooled system
- Economic analysis (initial cost, annual energy, operating and maintenance cost, scrap value, economic life, discount rate)
- Conclusion
Publication details
- Authors
- Meltem Ağaoğlu
- Publisher
- Yıldız Teknik Üniversitesi
- Year
- 2024
- Document language
- Turkish
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
University publisher metadata and open PDF read through its public stable file resolver. A short-lived signed object URL was not used as the library URL. Direct YÖK full-text access was not verified.
Citation
Meltem Ağaoğlu (2024). Veri Merkezi Beyaz Alanının Şartlandırılmasında Hava Soğutmalı ve Daldırmayla Sıvı Soğutmalı Sistemlerin Enerji Tüketimi ve Ekonomik Analizi. Yıldız Teknik Üniversitesi. https://avesis.yildiz.edu.tr/dosya?id=96ab15a2-ff51-470e-a784-94dd3da039fd
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
