Liquid Cooling - When performance meets sustainability: the data center cooling challenge
STULZ
STULZ presents direct-to-chip and immersion liquid cooling as a response to AI rack densities and European efficiency regulation. Three CDU heat-exchanger selections at 1 MW show the trade-off between approach temperature, heat-exchanger area and TCS flow.
On this page
Overview
The introduction says NVIDIA Blackwell-class systems push rack densities from 70 kW toward 120 kW and that liquid is up to about 1,000 times more effective than air as a heat carrier. On regulation it cites the German Energy Efficiency Act: existing DCs PUE 1.5 from July 2027 and 1.3 from July 2030, DCs starting from 1 July 2026 must reach 1.2, and EU reporting applies from 500 kW IT.
Direct-to-chip removes 70-90 % of rack heat via liquid and the remaining 10-30 % by air. For temperatures, practical TCS regimes cited are 35/25 and 36/26 C; liquid-cooling return temperatures of up to about 60 C support heat reuse, and heat pumps can lift these to about 75 C.
Three worked cases are for a 1,000 kW CDU. Case 1: FWS 22/32 C water, TCS 36/26 C PG25, APT 4 K, heat-exchanger area 71.8 m2. Case 2: the same duty with APT 2 K needs 143.6 m2, double the area. Case 3: with APT 2 K but TCS delta-T raised to 15 K (39/24 C) the area stays 71.8 m2 and TCS flow falls 33 % (25.3 to 16.9 m3/h). The paper reflects a manufacturer view and its conclusions rest on these three cases.
Key points
- Blackwell-class systems push rack densities from 70 kW toward 120 kW; liquid is up to about 1,000x more effective than air as a heat carrier.
- German Energy Efficiency Act: existing DCs PUE 1.5 from July 2027 and 1.3 from July 2030; DCs starting from 1 July 2026 must reach 1.2; EU reporting from 500 kW IT.
- Direct-to-chip removes 70-90 % of rack heat via liquid, 10-30 % by air.
- Case 1: 1,000 kW CDU, FWS 22/32 C, TCS 36/26 C PG25, APT 4 K, heat-exchanger area 71.8 m2.
- Case 2: same duty with APT 2 K needs 143.6 m2 (double).
- Case 3: APT 2 K with TCS delta-T 15 K (39/24 C) keeps 71.8 m2 and cuts TCS flow 33 % (25.3 to 16.9 m3/h).
- Return temperatures up to about 60 C support heat reuse; heat pumps can lift them to about 75 C.
Using it in design
- Compare approach temperature, heat-exchanger area and TCS temperature difference together when selecting a CDU, using Cases 1–3 to check the calculation.
- Default the liquid fraction for D2C racks to 70-90 % and size the residual air load from the remainder.
- Show German EnEfG PUE targets by commissioning date, and flag sites of 500 kW IT or more for EU EED reporting.
Who should read it
Designers selecting CDUs for direct-to-chip AI facilities and tracking European efficiency rules.
Related standards
- German Energy Efficiency Act (EnEfG)
- EU Energy Efficiency Directive 2023/1791
- ASHRAE TC 9.9
Publication details
- Authors
- STULZ
- Publisher
- STULZ
- Year
- 2025
- Document number
- Release 31, January 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
STULZ (2025). Liquid Cooling - When performance meets sustainability: the data center cooling challenge. STULZ. Release 31, January 2025. https://www.stulz.com/fileadmin/user_upload/Documents/Downloads/Whitepaper/STULZ_Whitepaper_Liquid_Cooling_2503_EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.