Technical guideFree to read2025

Liquid Cooling - When performance meets sustainability: the data center cooling challenge

STULZ

STULZ presents direct-to-chip and immersion liquid cooling as a response to AI rack densities and European efficiency regulation. Three CDU heat-exchanger selections at 1 MW show the trade-off between approach temperature, heat-exchanger area and TCS flow.

On this page

Overview

The introduction says NVIDIA Blackwell-class systems push rack densities from 70 kW toward 120 kW and that liquid is up to about 1,000 times more effective than air as a heat carrier. On regulation it cites the German Energy Efficiency Act: existing DCs PUE 1.5 from July 2027 and 1.3 from July 2030, DCs starting from 1 July 2026 must reach 1.2, and EU reporting applies from 500 kW IT.

Direct-to-chip removes 70-90 % of rack heat via liquid and the remaining 10-30 % by air. For temperatures, practical TCS regimes cited are 35/25 and 36/26 C; liquid-cooling return temperatures of up to about 60 C support heat reuse, and heat pumps can lift these to about 75 C.

Three worked cases are for a 1,000 kW CDU. Case 1: FWS 22/32 C water, TCS 36/26 C PG25, APT 4 K, heat-exchanger area 71.8 m2. Case 2: the same duty with APT 2 K needs 143.6 m2, double the area. Case 3: with APT 2 K but TCS delta-T raised to 15 K (39/24 C) the area stays 71.8 m2 and TCS flow falls 33 % (25.3 to 16.9 m3/h). The paper reflects a manufacturer view and its conclusions rest on these three cases.

Key points

  1. Blackwell-class systems push rack densities from 70 kW toward 120 kW; liquid is up to about 1,000x more effective than air as a heat carrier.
  2. German Energy Efficiency Act: existing DCs PUE 1.5 from July 2027 and 1.3 from July 2030; DCs starting from 1 July 2026 must reach 1.2; EU reporting from 500 kW IT.
  3. Direct-to-chip removes 70-90 % of rack heat via liquid, 10-30 % by air.
  4. Case 1: 1,000 kW CDU, FWS 22/32 C, TCS 36/26 C PG25, APT 4 K, heat-exchanger area 71.8 m2.
  5. Case 2: same duty with APT 2 K needs 143.6 m2 (double).
  6. Case 3: APT 2 K with TCS delta-T 15 K (39/24 C) keeps 71.8 m2 and cuts TCS flow 33 % (25.3 to 16.9 m3/h).
  7. Return temperatures up to about 60 C support heat reuse; heat pumps can lift them to about 75 C.

Using it in design

  • Compare approach temperature, heat-exchanger area and TCS temperature difference together when selecting a CDU, using Cases 1–3 to check the calculation.
  • Default the liquid fraction for D2C racks to 70-90 % and size the residual air load from the remainder.
  • Show German EnEfG PUE targets by commissioning date, and flag sites of 500 kW IT or more for EU EED reporting.

Who should read it

Designers selecting CDUs for direct-to-chip AI facilities and tracking European efficiency rules.

Related standards

  • German Energy Efficiency Act (EnEfG)
  • EU Energy Efficiency Directive 2023/1791
  • ASHRAE TC 9.9

Publication details

Authors
STULZ
Publisher
STULZ
Year
2025
Document number
Release 31, January 2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

STULZ (2025). Liquid Cooling - When performance meets sustainability: the data center cooling challenge. STULZ. Release 31, January 2025. https://www.stulz.com/fileadmin/user_upload/Documents/Downloads/Whitepaper/STULZ_Whitepaper_Liquid_Cooling_2503_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.