Data Centre Guide (Nkom, Norway)

Original title Datasenterveileder

Norwegian Communications Authority (Nkom)

Norway's Nkom guide explains registration, security management, exercise and incident notification duties for data centres above 0.5 MW subscribed power under the ekom act in force from 1 January 2025.

On this page

Overview

The guide explains how the Norwegian electronic communications act (ekomloven), in force since 1 January 2025, and the data centre regulation (datasenterforskriften) govern the security and preparedness of data centres in Norway. The page version is dated 1 June 2026. The audience is commercial data centre operators and organisations running in-house data centres covered by the rules; the guide also draws its boundary against other regulation, such as colocation in telecom rooms.

Scope covers those who provide data centre services for payment and those operating a data centre above a subscribed electrical power threshold of 0.5 MW. Subscribed power is the legally allocated grid power, set by NVE concessions. The threshold is absolute, and the registration duty arises when it is exceeded. Crypto-mining data centres are covered; those of the defence sector, police and the Police Security Service are exempt. Operators must register with Nkom before starting up.

The security section consists of functional requirements: a documented security management system, risk and vulnerability assessment, baseline protection and damage limitation measures, security plans, written contingency plans and exercises, following up that subcontractors meet security requirements, and incident notification. If services stop, Nkom may order prioritisation of services and may require national autonomy.

The guide is a legal interpretation text; it describes the structure of obligations rather than technical detail. It shows the compliance framework for those designing or operating data centres in Norway and serves elsewhere as a reference example of regulatory design.

Key points

  1. The data centre provisions of the ekom act entered into force on 1 January 2025; the guide page version is dated 1 June 2026.
  2. Scope: those providing data centre services for payment and those operating data centres above 0.5 MW subscribed electrical power (including in-house data centres).
  3. Subscribed electrical power is the legally allocated grid power; the threshold is absolute and the registration duty arises once exceeded.
  4. Operators running several small data centres whose total exceeds the threshold are also covered; one facility can have several obligated operators.
  5. Crypto-mining data centres are covered; the defence sector, police and Police Security Service are exempt.
  6. Operators must register with Nkom before starting; registration includes subscribed power and an estimate of the share of power used for crypto mining.
  7. Regulation requirements: security management system, risk and vulnerability assessment, baseline protection and damage limitation, security plans, contingency plans and exercises, security audit, subcontractor follow-up and incident notification.
  8. Operators notify Nkom without undue delay of significant breaches, update the notice on material changes and on normalisation, and notify customers of planned work.

Using it in design

  • For Norwegian projects, assess subscribed power demand against the 0.5 MW threshold early and add the Nkom registration before operation to the project schedule.
  • Tie the documented security management system, value and risk assessment and baseline protection and damage limitation measures to architectural decisions.
  • Prepare an operating documentation structure in which contingency plans and exercises can be recorded in writing.
  • Add subcontractor and supplier security requirements to contracts and define how they are monitored.
  • Write the responsible persons, rapid notification channel and customer information flow for incident notification into the operating procedure.

Who should read it

Organisations designing or operating data centres in Norway, compliance managers and policy teams comparing regulatory frameworks.

Document contents

  1. Purpose and scope of the regulation
  2. Registration duty in law and regulation
  3. Security and preparedness: security requirements in the ekom act
  4. Security and preparedness: security requirements in the data centre regulation
  5. Supervision

Publication details

Authors
Norwegian Communications Authority (Nkom)
Publisher
Norwegian Communications Authority (Nkom)
Year
2025
Document language
Norwegian
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public publisher text inspected. No document-specific commercial redistribution permission established; metadata and original short summaries only.

Citation

Norwegian Communications Authority (Nkom) (2025). Datasenterveileder. Norwegian Communications Authority (Nkom). https://nkom.no/datasenter/datasenterveileder

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.