Large Quick Connector Specification, Version 2.0.0

Original title Large Quick Connector Specification, Version 2.0.0 (effective 15 July 2026)

Open Compute Project Foundation · Meta (G. Charest, E. Chen, D. Daniel, J. Fernandes et al.), Parker Hannifin et al.

OCP LQC v2.0.0 (15 July 2026) defines pressure-drop, torque, leakage, temperature and mechanical-dimension requirements for 1-inch liquid cooling quick connectors, ensuring multi-vendor interoperability.

On this page

Overview

The Large Quick Connector (LQC) Specification version 2.0.0 is effective from 15 July 2026. Authors are experts from Meta, Parker Hannifin, Safeway and CEJN. Version 1.0 (2023) was updated by Meta to comply with the OCP template; version 2.0.0 added pressure-drop and dry-torque tests and several new criteria to the performance requirements section. The aim is that plug and socket pairs from different manufacturers mate with each other; interoperability testing requires at least three suppliers with three production sets each.

Performance tests: 6.1 pressure drop (50 PSIG, 25% propylene glycol-water, 35°C, both flow directions, 20-100 LPM); 6.2 dry torque (<5 Nm on the first 5 connections and average <5 Nm after 100 connect-disconnect cycles); 6.3 wet torque (50 PSIG, <10 Nm); 6.4 elevated flow mate cycle test (plug side 55 PSIG, socket side 0 PSIG, 83 LPM, not above 200 LPM, 25.4 mm EPDM hose, 20 repeats of 5 connections); 6.5 fluid loss (14.5 and 50 PSIG, <0.15 mL per disconnect, ISO 18869:2017); 6.6 air inclusion (<2 mL/cycle).

Environmental tests: operating temperature (62°C at 15% RH for 16 hours; -5°C for 16 hours; PG25), non-operating temperature (72°C for 72 hours; -42°C for 72 hours), ASTM B117 salt spray (72 hours) and a leak-free 150 PSI hydrostatic check of at least 3 minutes after each. The hydrostatic pressure test is 300 PSIG for 3 minutes.

Mechanical form: ACME-2G 2-4 Stub external (socket) and internal (plug) threads, a Higbee cut to prevent cross-threading, a G1 (BSPP 1 inch) female thread at both ends, 0.5-1.0 mL of Krytox GPL 203 or Christo-lube MCG 114 on the first three plug sleeve threads, sleeve hardness of at least 50 HRC with 0.018 mm effective case depth and mounting torque of at least 150 N-m on stainless ports. Wetted materials are 300 series and 17-7 stainless steel and EPDM seals meeting UL 62368-2 flammability. Part markings are mate direction, manufacturer and "OCP LQC PLUG/SOCKET" text with optional red-blue ring colour coding. Safety: hydrostatic strength of three times normal working pressure (300 PSI) and two times after a single fault (150 PSI).

Key points

  1. Version 2.0.0 effective 15 July 2026; authors Meta, Parker Hannifin, Safeway and CEJN.
  2. Pressure drop test: 50 PSIG, 25% propylene glycol-water, 35°C, 20-100 LPM, both flow directions.
  3. Dry torque: <5 Nm on the first 5 connections; average <5 Nm after 100 cycles. Wet torque: <10 Nm.
  4. Elevated flow mate test: plug 55 PSIG, socket 0 PSIG, 83 LPM (maximum 200 LPM).
  5. Fluid loss: <0.15 mL per disconnect; air inclusion: <2 mL/cycle.
  6. Operating temperature tests at 62°C and -5°C; non-operating 72°C and -42°C; salt spray 72 hours.
  7. Hydrostatic: 300 PSIG for 3 minutes; 150 PSI after a single fault.
  8. Threads are ACME-2G 2-4 Stub with Higbee cut; end connection G1 (BSPP 1 inch) female.
  9. Plug sleeve at least 50 HRC; port mounting torque at least 150 N-m (stainless).
  10. Wetted material is 300 series and 17-7 stainless steel; seals are EPDM.

Using it in design

  • Specify rack manifold and server connections with OCP LQC compliant plug and socket; prefer products with interoperability testing from at least three suppliers.
  • Add the LQC pair pressure drop (20-100 LPM, PG25, 35°C curve) to hose and manifold pressure drop calculations.
  • Consider connect-disconnect effort (<5 Nm dry, <10 Nm wet) when designing service procedures and operator access.
  • Carry the leakage criterion (<0.15 mL per disconnect) and air inclusion (<2 mL/cycle) into the drip tray and air purge plan.
  • Write plug sleeve lubrication and G1 port mounting torque (150 N-m) into assembly and maintenance instructions; verify EPDM seal compatibility with PG25 and treated water.

Who should read it

Designers and suppliers selecting and specifying liquid cooling quick connectors for rack manifolds, CDUs and servers.

Document contents

  1. License
  2. Compliance with OCP Tenets
  3. Version Table
  4. Scope
  5. Overview (Terms and Definitions)
  6. Performance Requirements
  7. Mechanical Form (Mating Thread, End Terminations, Thread Lubrication, Hardening, Mounting Torque)
  8. Materials
  9. Part Markings
  10. Safety and Regulatory
  11. Appendix: LQC Torque Testing Guidelines
  12. Appendix: LQC Elevated Flow Mate Cycle Test Guidelines

Related standards

  • ISO 18869:2017
  • OCP UQD v2.0.0
  • OCP BMQC

Publication details

Authors
Meta (G. Charest, E. Chen, D. Daniel, J. Fernandes et al.); Parker Hannifin; Safeway; CEJN
Publisher
Open Compute Project Foundation
Year
2026
Document number
Version 2.0.0
Document language
English
Source type
Industry body
Access
Free to read
Licence
OWFa 0.9: Open Compute open specification licence; redistribution permitted
Original licence note

Section 1.1: contributions under Modified OWFa 0.9 (as of 16 Oct 2024); usage governed by the Modified OWFa 0.9 FSA. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Meta (G. Charest, E. Chen, D. Daniel, J. Fernandes et al.); Parker Hannifin; Safeway; CEJN (2026). Large Quick Connector Specification, Version 2.0.0 (effective 15 July 2026). Open Compute Project Foundation. Version 2.0.0. https://www.opencompute.org/documents/large-quick-connector-specification-version-2-0-0-final-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.