Technical guideFree to read2024

Open Rack V3 Blind Mate Quick Connector Specification (BMQC), Rev 1.0

Original title Open Rack V3 Blind Mate Quick Connector Specification (BMQC), Revision 1.0 (4 June 2024)

Open Compute Project Foundation · Glenn Charest (Meta), John Fernandes (Meta) et al.

OCP's 4 June 2024 BMQC specification defines supplier-interoperable blind mate valves: 50 psig working pressure, up to 9 L/min flow, 150 psig hydrostatic test and 120 mate cycles.

On this page

Overview

The specification standardises the form, fit and function of blind mate quick connectors (BMQC) for Open Rack V3 so that valves from different suppliers interoperate. ORv3 liquid cooling support, with blind mate connections, reduces service time and offers layout advantages over manual connections. Authors come from Meta, SafeWay, Wiwynn, Parker, CEJN and Danfoss.

The design needs enhanced radial misalignment allowance, angular offset allowance, gatherability and stroke, driven by IT gear to rack interfaces, frame manufacturing, mate forces, load deflection, thermal expansion and manufacturing tolerances. The solution achieves this float with a self-contained floating body and no add-on components, so internal tubing selection for the plug and tubing management inside the IT gear are critical.

Functional parameters: maximum working pressure 3.45 bar (50 psig), maximum flow 9 L/min, hydrostatic pressure 150 psig (coupled and uncoupled), O-ring blow-out 55 psig, air inclusion 0.1 mL/cycle, spillage 0.025 cm³ at 0 psig and 0.05 cm³ at 50 psig. The solution is developed for a maximum fluid temperature of 60 °C; pressure drop requirements are set at 40 °C supply with Dowfrost LC25 (25% propylene glycol-water) and must be met in both flow directions. The test chapter describes many cycle and pressure tests (for example 120 and 36 cycle series, a 240-cycle mated pair test, 5.25 mm radial offset).

Key points

  1. Dated 4 June 2024, Revision 1.0.
  2. The goal is interoperability of blind mate valves from different suppliers.
  3. Maximum working pressure 3.45 bar (50 psig); maximum flow 9 L/min.
  4. Hydrostatic pressure 150 psig (coupled and uncoupled); O-ring blow-out 55 psig.
  5. Spillage 0.025 cm³ at 0 psig and 0.05 cm³ at 50 psig; air inclusion 0.1 mL/cycle.
  6. Maximum fluid temperature 60 °C; pressure drop requirement set at 40 °C Dowfrost LC25 in both flow directions.
  7. Testing: one valve pair must pass 120 cycles, another 36 cycles; mated pair test is 240 cycles including 5.25 mm radial offset.
  8. Floating body and large misalignment tolerance make internal tubing selection critical.
  9. Interoperability is tested across all supplier combinations.

Using it in design

  • Select BMQC for rack connections against the 50 psig and 9 L/min limits and add branches if branch flow exceeds the limit.
  • Choose the internal hose on the plug so it suits the floating body and does not bend or carry load.
  • Run pressure drop calculations at 40 °C and 25% propylene glycol-water conditions.
  • Ask purchasing for ORv3 BMQC compliance and the supplier interoperability test report.
  • Add air inclusion and spillage limits (0.1 mL/cycle, 0.05 cm³) to the service procedure as acceptance criteria.

Who should read it

OCP ORv3 rack and server designers, quick connector manufacturers and liquid cooling procurement teams.

Document contents

  1. License
  2. Compliance with OCP tenets
  3. Version table
  4. Scope
  5. Overview
  6. Rack compatibility
  7. Design basics
  8. Mechanical design specifications
  9. Functional parameters
  10. Tubing interfaces and considerations
  11. Test requirements and methodology
  12. Test fixture requirements
  13. Environmental regulations
  14. Safety
  15. Prescribed materials
  16. References

Related standards

  • OCP Open Rack V3
  • OCP UQD
  • ISO 18869

Publication details

Authors
Glenn Charest (Meta); John Fernandes (Meta); Nick Goenner (SafeWay); Chris Lee (Wiwynn); Tim Marquis (Parker); Noman Mithani (Meta); Andy Holst (Parker); Emil Pettersson (CEJN); Amit Shende (Danfoss)
Publisher
Open Compute Project Foundation
Year
2024
Document number
Rev 1.0
Document language
English
Source type
Industry body
Access
Free to read
Licence
OWFa 1.0: Open Compute open specification licence; redistribution permitted
Original licence note

Section 1: contributions under OWF CLA 1.0, usage under OWFa 1.0 Specification License. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Glenn Charest (Meta); John Fernandes (Meta); Nick Goenner (SafeWay); Chris Lee (Wiwynn); Tim Marquis (Parker); Noman Mithani (Meta); Andy Holst (Parker); Emil Pettersson (CEJN); Amit Shende (Danfoss) (2024). Open Rack V3 Blind Mate Quick Connector Specification (BMQC), Revision 1.0 (4 June 2024). Open Compute Project Foundation. Rev 1.0. https://www.opencompute.org/documents/orv3-blind-mate-quick-connector-specification-rev01-04june2024-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.