White paperFree to read2015

Universal Aisle Containment: Increased Efficiency with Fewer Deployment Restrictions

Original title Universal Aisle Containment: Increased Efficiency with Fewer Deployment Restrictions (White Paper)

Panduit · Panduit Corp.

A Panduit white paper (April 2015) reporting that its Net-Contain UAC, installable as cold or hot aisle containment, matches cabinet-mounted containment in thermal performance, tested up to 25 kW per cabinet.

On this page

Overview

The paper points to restrictions that block containment in existing data centers (only the provider's cabinets, different cabinet heights and widths) and to the need in new sites to fully populate rows on day one. Panduit's Net-Contain Universal Aisle Containment (UAC) can be deployed as cold or hot aisle containment, works with several cold air delivery methods, and can contain rows of cabinets of different heights, widths and manufacturers, including unpopulated or partially populated rows.

Tests ran in Panduit's thermal lab: 1,600 ft² white space, 36 in raised floor, 12 ft ceiling with above-ceiling hot air return. Two rows of five 600 × 1,200 mm 45 RU cabinets with 56% open perforated front doors and load banks were used; supply set point was 75 °F (23.9 °C) with best-practice airflow management (blanking panels, grommets, air dams, skirts). Four configurations were compared: uncontained hot/cold aisle, cabinet-mounted CAC, 3,000 mm UAC-CAC, and 4,800 mm UAC-CAC with 1,800 mm of unpopulated aisle blanked. Three loads were tested per cabinet: 4.5 kW (600 CFM), 15 kW (1,800 CFM) and 25 kW (3,000 CFM).

To normalize conditions the study used a 'critical air ratio' (CAR): the ratio of cooling unit airflow to IT airflow, taken as the largest of the minimum ratio giving inlet temperatures at the ASHRAE recommended 80.6 °F (27 °C), a ratio of 1, and for CAC the minimum ratio keeping the cold aisle 0.002 in H2O (0.50 Pa) above the room. All contained configurations stayed at least 1.4 °F below the maximum, with UAC performing nearly identically to cabinet-mounted containment.

The uncontained layout approached acceptable inlet temperatures only at the lowest load, while UAC and cabinet-mounted CAC easily cooled the highest 25 kW load. The uncontained CAR was 6% to 8% higher than the contained ones. Equivalent performance of UAC as HAC is stated to have been verified, and containment energy savings of as much as 30% are cited when the entire cooling chain is considered. The document is a vendor publication.

Key points

  1. UAC can be installed as cold or hot aisle containment and accommodates mixed cabinet heights, widths and manufacturers and empty or partly filled rows.
  2. Test lab: 1,600 ft², 36 in floor, 12 ft ceiling; supply set point 75 °F (23.9 °C).
  3. Two rows of five cabinets (600 × 1,200 mm, 45 RU), 56% open perforated front doors; loads 4.5 kW (600 CFM), 15 kW (1,800 CFM), 25 kW (3,000 CFM) per cabinet.
  4. CAR is the largest of: ratio needed for ASHRAE 80.6 °F (27 °C) inlet, 1, and for CAC +0.002 in H2O (0.50 Pa) in the cold aisle.
  5. For contained configurations inlet temperatures at 4.5 kW were 2.9 °F or more below the maximum, spread about 2.6 °F; at 15 and 25 kW at least 1.4 °F below, spread about 3.8 °F.
  6. Uncontained hot/cold aisle CAR was 6% to 8% higher than the contained configurations.
  7. The uncontained layout only approached acceptable inlet temperatures at the lowest load; UAC and cabinet-mounted CAC cooled 25 kW.
  8. Containment savings can reach 30% when the entire cooling chain is taken into account.

Using it in design

  • For existing rooms with mixed cabinet heights and widths, evaluate aisle containment options not tied to one manufacturer's cabinets.
  • For rows not fully populated on day one, plan expandable containment where unpopulated sections are closed with full-height blanking panels.
  • In contained rooms keep supply airflow close to IT airflow and monitor air ratio (CAR) and cold aisle positive pressure.
  • In cold aisle containment hold a small positive pressure against the room (0.50 Pa in the test) so leakage is cold air out rather than hot air in.
  • At acceptance testing at target cabinet loads (4.5, 15, 25 kW) verify inlet temperature stays below 27 °C.

Who should read it

Mechanical designers selecting containment and operations teams of existing mixed-cabinet rooms.

Document contents

  1. Introduction
  2. Containment performance: test facility
  3. Testing approach
  4. Test setup
  5. Test procedures
  6. Test results: inlet temperatures
  7. Critical air ratio
  8. UAC-HAC and UAC-CAC equivalent performance
  9. Conclusion

Related standards

  • ASHRAE TC 9.9 thermal guidelines

Publication details

Authors
Panduit Corp.
Publisher
Panduit
Year
2015
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

©2015 Panduit Corp. All Rights Reserved; copy hosted by distributor (Sonepar)

Citation

Panduit Corp. (2015). Universal Aisle Containment: Increased Efficiency with Fewer Deployment Restrictions (White Paper). Panduit. https://res.cloudinary.com/sonepar-fr/raw/upload/s--sNbS1CKC--/v1/documents/156/100662285.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.