White paperFree to read2023

The Power of 10: Powering 10 MW-100 MW Microgrids and beyond (White Paper)

Piller / Langley Holdings Power Solutions Division

A Piller / Langley Holdings Power Solutions Division white paper on a modular microgrid approach that parallels 10.8 MW Bergen gensets up to 100 MW with Piller integrated power conditioning built from 4 x 2.5 MW modules.

On this page

Overview

The white paper presents 10 MW-plus gensets as modular building blocks that replace the grid. The solution combines Bergen medium-speed engine gensets, Marelli Motori 10 MW alternators and Piller Integrated Power Conditioning Technology (IPCT). Bergen's largest single genset delivers 10.8 MW, and sets parallel to more than 100 MW in a grow-as-you-need pattern. The engines are hydrogen ready, with a road map from diesel to LNG, LNG/hydrogen blend and pure hydrogen.

The technical argument is that rotating machines with batteries behave differently from IGBT inverters with batteries and provide different stability. The 10 MW IPCT comprises four 2.5 MW Piller UB-V modules coupled to the power module through a single 10 MW choke; it provides frequency stabilisation and voltage support, protects against grid outages and synchronises during planned coupling and decoupling. Grid forming, constant short circuit ratio (SCR) and inertia ease fault management, and the grid-gate choke blocks exchange of short-circuit power between two grids.

A theoretical case study defines a microgrid for a town of 10,000-15,000 people with 10 MWp of wind, 6 MWp of solar, 3 x 5.3 MW gas gensets and a 5 MW/10 MWh battery. The design brief requires operation with no renewable input and no utility import. It is a vendor publication; data centres appear among microgrid users but no data-centre-specific design is given.

Key points

  1. Bergen's largest single genset delivers 10.8 MW; sets parallel to 100 MW and beyond.
  2. 10 MW IPCT: four 2.5 MW Piller UB-V modules coupled to the power module through a single 10 MW choke.
  3. IPCT comes in two options: island microgrid and grid-connected.
  4. With an engine in the system black start is possible; the grid-gate choke blocks exchange of short-circuit power between grids.
  5. Case study: 10 MWp wind, 6 MWp solar, 3 x 5.3 MW gas sets, 5 MW/10 MWh battery; designed to run with no utility import and no renewables.
  6. Rotating machines provide constant SCR and natural inertia, behaving differently from inverter-and-battery systems.
  7. Bergen engines are medium speed, offer low-load continuous running and hot standby, and are hydrogen ready.
  8. By 2050 the planet's 40,000 TWh of electricity is stated to need 90% from renewable and nuclear sources.

Using it in design

  • In grid-constrained regions, assess a genset-based microgrid for a data-centre campus in terms of 10 MW modular blocks and parallel expansion.
  • For systems dominated by inverter-based sources, analyse short-circuit ratio (SCR) and inertia separately and decide whether rotating machines or a frequency/voltage conditioning module are needed.
  • Define and test transitions between island and grid-connected modes (grid-following and grid-forming) as scenarios.
  • Add to the commissioning and simulation plan that inverter and battery components from different suppliers may have unknown response times.
  • The paper is a vendor view; verify the fuel and emissions road map separately against local regulation and fuel supply.

Who should read it

Electrical engineers, EPC and investor teams designing large microgrids, islanded energy systems or grid-alternative facilities.

Document contents

  1. Executive summary
  2. Why microgrid?
  3. Power Solutions Division approach
  4. Characteristics of the Power Solutions Division approach
  5. Microgrid application example: case study
  6. Conclusion
  7. Appendix: microgrid players, definition and modes

Related standards

  • ISO 8528-1

Publication details

Authors
Piller / Langley Holdings Power Solutions Division
Publisher
Piller / Langley Holdings Power Solutions Division
Year
2023
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Vendor white paper from piller.com downloads; no open licence. Year from PDF metadata (Apr 2023).

Citation

Piller / Langley Holdings Power Solutions Division (2023). The Power of 10: Powering 10 MW-100 MW Microgrids and beyond (White Paper). Piller / Langley Holdings Power Solutions Division. https://www.piller.com/wp-content/uploads/2024/01/Power-of-10-Microgrids-White-Paper.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.