Technical guideFree to readYear not stated

MegaFlex DPA 250-6000 kW: IEC and CSB Technical Specifications

Original title MegaFlex DPA 250–6000 kW: IEC and CSB technical specifications

ABB

ABB MegaFlex DPA is a three-phase modular UPS built from 250 kW modules, scaling to 2000 kW per frame and 6000 kW in parallel, with VFI efficiency up to 97.4% and up to 99% in eco mode.

On this page

Overview

ABB's MegaFlex DPA brochure presents an online double-conversion modular UPS family from 250 to 6000 kW. The system is based on ABB's decentralized parallel architecture (DPA): each power module has all the functional units needed for independent operation, so the system can be sized exactly to need and, in an N+1 setup, the other modules take the load if one fails. Modules can be added or removed without powering down. Design life is up to 15 years.

Power frames sit in 1000, 1500 and 2000 kW connection frames. The IEC version has system ratings of 1000, 1250 and 1500 kW with a distributed static bypass architecture, reaching 6000 kW in parallel with 6 x 1000 kW or 4 x 1500 kW. The CSB version covers 1500, 1750 and 2000 kW with a centralized fault-tolerant pluggable static bypass and parallels up to 4500 kW (3 x 1500 kW) or 4000 kW (2 x 2000 kW). Topology is VFI-SS-111.

Input is 380/400/415 VAC with +15% at all loads and -30% at partial loads, THDi below 3% and power factor 0.99. Output voltage is ±1%, THDu below 2% and power factor 1.0. System-level efficiency reaches 97.4% (up to the 2 MW frame size), stays above 97% across load variation and reaches 99% in eco mode (VFD); the brochure body text gives 99.4% in eco mode. Xtra VFI mode adjusts the number of active modules dynamically at low load. Battery types VRLA, Li-Ion and nickel zinc are supported, with a decentralized charger per power module.

Key points

  1. 250 kW power module; up to 2000 kW per frame and 6000 kW in parallel (IEC).
  2. IEC: 1000, 1250, 1500 kW; distributed static bypass; 6 x 1000 kW or 4 x 1500 kW in parallel.
  3. CSB: 1500, 1750, 2000 kW; centralized static bypass; 3 x 1500 kW (4500 kW) or 2 x 2000 kW (4000 kW) in parallel.
  4. Topology VFI-SS-111; input power factor 0.99, THDi <3%; output power factor 1.0, THDu <2%.
  5. Efficiency: VFI up to 97.4% (>97% across load); up to 99% in eco mode (VFD).
  6. ABB example: a 10 MW IT-load 2N data centre over 15 years saves up to 38% energy against a legacy UPS at 96.3%, about 2.4 M euro.
  7. Protocols and interfaces: Modbus TCP/IP, RS-485, SNMP v2/v3, SMTP; remote shutdown, gen-set and external bypass contacts.
  8. Weight 1940 to 4600 kg; IP20; operation 0 to 40 °C; no derating up to 1000 m; seismic certifications ASCE 7-2016, IBC 2018, IEEE 693-2018.

Using it in design

  • Select frame size by N+1: the brochure gives examples of 750 kW N+1 up to 1000 kW, 1000 kW N+1 up to 1500 kW and 1750 kW N+1 up to 2000 kW.
  • Choose between distributed (IEC) and centralized (CSB) static bypass according to fault tolerance and maintenance approach.
  • Assess the effect of Xtra VFI mode on part-load efficiency against the operating load profile; losses are significant below 25% load.
  • In battery selection, account for VRLA, Li-Ion or nickel zinc options and the per-module charger.
  • For seismic regions, tie the brochure certifications (ASCE 7-2016, IEEE 693-2018) to the specification.
  • Include weight and footprint (for example 1500 kW: 3045 x 2000 x 1000 mm, 3250 kg) in floor-loading calculations.

Who should read it

Electrical designers and decision makers selecting high-power modular UPS systems for mid-size and large data centres.

Document contents

  1. Meet the best and most reliable UPS on the market
  2. The flexible approach
  3. Optimized efficiency
  4. Reliable operations
  5. High serviceability
  6. The MegaFlex DPA portfolio
  7. MegaFlex DPA IEC 400 V
  8. MegaFlex DPA IEC CSB 400 V
  9. The MegaFlex DPA as reliable and eco-friendly UPS
  10. Control and monitoring
  11. Test and trusted
  12. Services
  13. Technical specifications

Publication details

Authors
ABB
Publisher
ABB
Year
Year not stated
Document number
4NWP106478R0001_EN
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ABB MegaFlex DPA 250–6000 kW: IEC and CSB technical specifications. ABB. 4NWP106478R0001_EN. https://search.abb.com/library/Download.aspx?Action=Launch&DocumentID=4NWP106478R0001_EN&DocumentPartId=&LanguageCode=en

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.