Rule based control of data centre chillers
Original title Energy Efficiency Increase Achieved by Dedicated Rule-Based Control of Chillers Operating in the Data Center
Energies (MDPI AG) · Mateusz Borkowski, Adam Krzysztof Piłat
This 2022 Energies study develops a rule-based controller that switches operating modes of a data-centre chiller system; in 2017 experimental validation free cooling ran 2,064 h longer, COP rose 69% and 206.9 MWh was saved.
On this page
Overview
The study notes that commercial cooling solutions on the market use universal, generic control methods, which creates application limits. The authors therefore developed their own system architecture and a dedicated control algorithm. Historical data from an operating cooling system were analysed and, on that basis, a rule-based controller was built to switch operating modes correctly. The time constants of the automation actuators and the dynamics of the cooling process were identified.
The control strategy was experimentally validated throughout 2017. The solution allows individual control of each element of the cooling system. This extended free-cooling operation by 2,064 h over the year, raised the cooling system's COP by 69% and cut electricity consumption by 206.9 MWh through longer free-cooling operation. The savings describe the evaluated installation.
Key points
- A rule-based controller was developed from historical data of an operating system.
- Actuator time constants and cooling process dynamics were identified.
- The control strategy was experimentally validated throughout 2017.
- Free-cooling operation was extended by 2,064 hours per year.
- COP rose 69% and electricity consumption fell by 206.9 MWh.
Using it in design
- In free-cooling chiller systems, design an architecture that controls each element individually, with a mode-switching rule.
- Measure actuator time constants and process dynamics before setting control rule thresholds.
- Recompute the reported 69% COP gain and 206.9 MWh saving with your own facility's load and climate data.
Who should read it
Engineers designing chiller system control logic and free-cooling changeover strategies.
Publication details
- Authors
- Mateusz Borkowski; Adam Krzysztof Piłat
- Publisher
- Energies (MDPI AG)
- Year
- 2022
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Article-specific publisher copyright/rights statement explicitly grants CC BY; version 4.0 is corroborated by publisher-deposited Crossref license metadata. Third-party material may have separate rights. Round 3/4 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Mateusz Borkowski; Adam Krzysztof Piłat (2022). Energy Efficiency Increase Achieved by Dedicated Rule-Based Control of Chillers Operating in the Data Center. Energies (MDPI AG). https://doi.org/10.3390/en15072419