Montair TIP 1026-3120 technical data (dual-fluid DX close-control unit)
Original title Montair TIP 1026–3120 technical data
Montair
Montair TIP is a dual-fluid close-control unit from 26.0 to 122 kW with R410A, inverter scroll compressors and EC fans; the DX circuit gives 26.1-122 kW maximum total capacity across five models.
On this page
Overview
The TIP family combines an air-cooled direct-expansion (DX) circuit and a chilled-water circuit in one unit. The two circuits are separate and do not start together, which gives back-up operation. The refrigerant is R410A, the compressor is inverter scroll and the fans are EC inverter plug-fans; an electronic expansion valve is standard.
The manufacturer states that the inverter compressor and EC fans adjust power to the real thermal load, with up to 88 % difference between minimum and maximum absorbed power. Two versions exist: TIPT (top discharge, front intake) and TIPB (bottom discharge, top intake). Models are 1026, 1048, 2061, 2087 and 3120.
The data table gives maximum and minimum total and sensible capacity, SHR, absorbed power and EER for the DX circuit. Maximum total capacity is 26.1, 49.5, 62.5, 89.6 and 122 kW and maximum sensible capacity is 20.2, 37.8, 52.7, 72.2 and 93.5 kW. Chilled-water circuit capacity is 16.8, 38.7, 57.3, 79.6 and 99.5 kW (7/12 °C water).
The page also lists air flow (5,200 to 24,000 m³/h), available static pressure, M5 filters, 400/3+N/50 supply, sound pressure (66-73 dB(A) for TIPT, 60-66 for TIPB), dimensions, weights and a long accessory list. Capacity figures apply to 24 °C and 50 % RH ambient air with a 45 °C condensing temperature.
Key points
- Power range 26.0-122 kW; R410A, inverter scroll compressor, EC inverter plug-fans.
- DX circuit maximum total capacity: 26.1 / 49.5 / 62.5 / 89.6 / 122 kW (1026 / 1048 / 2061 / 2087 / 3120).
- Maximum sensible capacity 20.2 / 37.8 / 52.7 / 72.2 / 93.5 kW; maximum EER 3.40-3.63.
- Chilled-water circuit total capacity 16.8 / 38.7 / 57.3 / 79.6 / 99.5 kW; water flow 0.80-4.70 l/s, pressure drop 33-47 kPa (7/12 °C).
- Air flow 5,200-24,000 m³/h (at 20 Pa static pressure); maximum available static pressure with standard fans 250-350 Pa.
- Sound pressure 66-73 dB(A) for TIPT and 60-66 dB(A) for TIPB (ISO 3744, 2 m).
- Operating weight 301-1,074 kg; length 875-2,625 mm, width up to 890 mm, height 1,980 mm.
- Communication options: Modbus TCP/IP, BACnet IP and MSTP (BTL certified), SNMP.
Using it in design
- Check total and sensible capacity separately; both apply to the stated ambient and condensing conditions and must be recalculated for other temperatures.
- Treat the dual-fluid design as a chilled-water back-up: DX and water circuits do not run together, so confirm each can carry the load alone.
- Check raised-floor load capacity and service clearance against the unit weights and dimensions.
- Select the Modbus TCP, BACnet or SNMP option at order stage to match the BMS.
- Choose top or bottom discharge (TIPT or TIPB) to suit the aisle and plenum arrangement.
Who should read it
Mechanical designers selecting close-control units, and BMS integrators.
Document contents
- Product description and versions
- Power range
- Factory-fitted and loose accessories
- Technical data (DX circuit, chilled-water circuit, fan section)
- Dimensions and weights
- Notes and documents
Publication details
- Authors
- Montair
- Publisher
- Montair
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Montair Montair TIP 1026–3120 technical data. Montair. https://montair.it/en/products/50-hz/direct-expansion-close-control-units-with-full-inverter-technology/air-cooled-direct-expansion-dual-fluid-units/tip-10263120
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.