Montair WOPR technical data (chilled-water in-row units)

Original title Montair WOPR technical data

Montair

Montair WOPR is a four-model, 300 mm wide 42U chilled-water in-row unit of 16-32 kW; at 10/15 °C water and 35 °C return air it delivers 15.7-32.4 kW.

On this page

Overview

The WOPR series is a range of chilled-water in-row units designed to sit close to the equipment generating the heat load in a data centre. They use EC plug-fans with backward-curved blades, and a large coil optimised for high inlet water temperature and a wide deltaT.

Load changes are met by a 2- or 3-way modulating valve acting together with automatic fan speed control, managed by a microprocessor and an advanced user interface. Five versions exist: front discharge (1000 or 1200 mm deep) and lateral discharge to both sides, the right or the left.

The table covers models 0015, 0020, 0025 and 0030. Total capacity is 15.7, 21.4, 26.0 and 32.4 kW, equal to sensible capacity (SHR 1). Air flow is 3,000-5,800 m³/h, fan consumption 0.26-0.65 kW, water flow 0.75-1.55 l/s and water-side pressure drop 35.7-55.4 kPa. Supply is 230/1/50.

The unit is 300 mm wide and 2,073 mm (42U) high with a 1000 or 1200 mm depth, weighing 186-216 kg. Capacity figures are for 35 °C, 25 % RH return air and 10/15 °C water. Options include a pressure-independent 2-way valve with flow meter, Modbus RTU/TCP, BACnet and SNMP.

Key points

  1. Four models, 16-32 kW class: total and sensible capacity 15.7 / 21.4 / 26.0 / 32.4 kW (SHR 1).
  2. Condition: return air 35 °C, 25 % RH; water 10/15 °C.
  3. Air flow 3,000 / 4,000 / 5,400 / 5,800 m³/h; fan consumption 0.26-0.65 kW.
  4. Water flow 0.75-1.55 l/s; pressure drop 35.7-55.4 kPa.
  5. Size 300 mm wide, 2,073 mm (42U) high; depth 1000 or 1200 mm; weight 186-216 kg.
  6. ISO 16890 filtration e(PM10) at least 50 %; supply 230/1/50.
  7. Options: pressure-independent 2-way valve with flow meter (MVP), 3-way valve, dual-power transfer switch, SNMP, BACnet, Modbus.

Using it in design

  • In row layouts, match capacity per row to the sensible load per rack; on this unit total and sensible capacity are equal.
  • Compare the coil's high-water-temperature, wide-deltaT design with the 10/15 °C regime of the chilled-water plant.
  • Order the pressure-independent valve with flow meter where monitoring needs flow measurement.
  • Allow for the row length and the 300 mm module width in the floor plan.

Who should read it

Mechanical engineers designing in-row cooling.

Document contents

  1. Product description and versions
  2. Power range
  3. Factory-fitted and loose accessories
  4. Technical data
  5. Dimensions and weights
  6. Notes and documents

Publication details

Authors
Montair
Publisher
Montair
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Montair Montair WOPR technical data. Montair. https://montair.it/en/products/50-hz/precision-in-row-in-rack-cooling-system/high-performing-chilled-water-in-row-conditioning-units/wopr-00150030

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.