Montair XIPR is a 42U direct-expansion in-row unit of 6.3-35.0 kW with R410A and an external inverter-scroll condensing unit; maximum capacity of the three models is 15.1, 23.1 and 35.0 kW.
On this page
Overview
The XIPR series is a range of direct-expansion in-row units placed close to the equipment that generates the heat. They use EC inverter plug-fans, an electronic expansion valve controlled by a microprocessor and an advanced user interface. The system is completed by an external condensing unit with a high-efficiency inverter scroll compressor; fans and compressor run on dedicated logics that raise efficiency across a wide operating range.
Models are 1015, 1025 and 1035. Maximum total capacity is 15.1, 23.1 and 35.0 kW and minimum is 6.3, 9.9 and 15.3 kW. Sensible capacity equals total capacity (SHR 100 %). Maximum air flow is 3,000, 4,000 and 5,800 m³/h, with minimum at half of that. Fan consumption is 0.26-0.64 kW at maximum and 0.05-0.12 kW at minimum.
For the external motor-condensing unit (MREI), compressor absorbed power is 4.75, 8.18 and 8.31 kW at maximum and 1.15, 1.78 and 2.28 kW at minimum. Maximum EER is 3.01, 2.70 and 3.91 and minimum EER is 3.02, 2.93 and 3.15. The indoor unit is supplied at 230/1/50 and the outdoor unit at 400/3+N/50.
The indoor unit is 300 mm wide and 2,073 mm (42U) high, with a 1000 or 1200 mm depth and a weight of 183-217 kg. The outdoor unit weighs 195-275 kg. Values apply to 35 °C, 25 % RH return air and 35 °C outdoor temperature. Five versions exist: front discharge and lateral discharge to both sides, right or left.
Key points
- Power range 6.3-35.0 kW; maximum total capacity 15.1 / 23.1 / 35.0 kW and minimum 6.3 / 9.9 / 15.3 kW.
- Sensible equals total capacity (SHR 100 %); condition: return air 35 °C / 25 % RH, outdoor 35 °C.
- Air flow 3,000 / 4,000 / 5,800 m³/h maximum, 1,500 / 2,000 / 2,900 m³/h minimum.
- Compressor absorbed power 4.75 / 8.18 / 8.31 kW maximum and 1.15 / 1.78 / 2.28 kW minimum.
- EER maximum 3.01 / 2.70 / 3.91, minimum 3.02 / 2.93 / 3.15.
- Indoor unit 300 x 1000-1200 x 2,073 mm, 183-217 kg; outdoor unit 195-275 kg.
- Fan and compressor modulation adjust power to load; refrigerant R410A.
Using it in design
- Check the minimum capacity (6.3-15.3 kW) against low-load rack rows; it sets the turn-down before cycling.
- Plan the position, weight (195-275 kg) and refrigerant line length of the external condensing unit early.
- The rating outdoor condition is 35 °C; reconfirm capacity from the catalogue for hotter ambient conditions.
- Separate the indoor (230/1/50) and outdoor (400/3+N/50) supplies on the distribution board.
Who should read it
Mechanical and electrical engineers designing DX in-row cooling.
Document contents
- Product description and versions
- Power range
- Factory-fitted and loose accessories
- Technical data
- Dimensions and weights
- Notes and documents
Publication details
- Authors
- Montair
- Publisher
- Montair
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Montair Montair XIPR technical data. Montair. https://montair.it/en/products/50-hz/precision-in-row-in-rack-cooling-system/direct-expansion-in-row-conditioning-units/xipr-10101035
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.