Montair WOP 0009-0155 technical data (chilled-water close-control units)
Original title Montair WOP 0009–0155 technical data
Montair
Montair WOP is a 19-model range of EC-fan chilled-water close-control units from 8.5 to 154 kW total capacity at 7/12 °C water, with up/down-flow versions.
On this page
Overview
The WOP range consists of chilled-water close-control units. The chilled water can come from a water-cooled or air-cooled chiller, including one with free-cooling. Flow through the unit coil is managed by an internal 3-way valve. Two airflow versions exist: WOPT (top discharge, front intake) and WOPB (bottom discharge, top intake).
Fans are EC inverter plug-fans, with high-head fans as an option. The manufacturer says EC fans cut consumption at partial load by up to 61 % compared with centrifugal fans. Standard supervision is Modbus RTU over RS485; Modbus TCP/IP, BACnet IP, BACnet MSTP (BTL certified) and SNMP are options.
For 19 models (0009, 0013, 0018 through 0155) the table gives total capacity from 8.5 to 154 kW, sensible capacity 7.7 to 119 kW, water flow 0.41 to 7.36 l/s and water-side pressure drop 37 to 51 kPa. Air flow ranges from 2,500 to 25,500 m³/h; maximum available static pressure is 160-550 Pa with standard fans and 400-895 Pa with high-ESP fans.
The electric heater has three steps (4.5 to 27 kW) and the electrode steam humidifier produces 4 to 15 kg/h. Dimensions are 675 to 2,625 mm long, 675 to 890 mm wide and 1,980 mm high. Capacities are quoted for 24 °C and 50 % RH ambient air with 7/12 °C water.
Key points
- 19 models, total capacity 8.5-154 kW (2.4-44 ton), sensible 7.7-119 kW (7/12 °C water, 24 °C / 50 % RH).
- Water flow 0.41-7.36 l/s; water-side pressure drop 37-51 kPa.
- Air flow 2,500-25,500 m³/h; maximum available static pressure 160-550 Pa with standard fans and 400-895 Pa with high-ESP fans (flow calculated at 20 Pa).
- EC fans are stated to cut partial-load consumption by up to 61 % against centrifugal fans.
- Standard communication Modbus RTU (RS485); options Modbus TCP/IP, BACnet IP, BACnet MSTP (BTL), SNMP.
- Electric heater 4.5-27 kW (3 steps); steam humidifier 4-15 kg/h (3-11.3 kW).
- M5 filters; small models are supplied at 230/1/50.
- Dimensions: length 675-2,625 mm, width 675-890 mm, height 1,980 mm.
Using it in design
- Server rooms are sensible-heat dominated; select the model by comparing sensible capacity (SHR 77-94 %) with the load, not total capacity.
- Recalculate capacity from the catalogue for water temperatures other than 7/12 °C; the table covers only that condition.
- Add the water flow and the 37-51 kPa pressure drop to the pipe and pump calculation.
- Choose the high-ESP fan option where ducted or plenum layouts need higher static pressure.
- Fix the BMS protocol (Modbus TCP, BACnet, SNMP) at order stage.
Who should read it
Mechanical designers selecting chilled-water close-control units, and BMS integrators.
Document contents
- Product description and versions
- Power range
- Factory-fitted and loose accessories
- Technical data
- Dimensions and weights
- Notes and documents
Publication details
- Authors
- Montair
- Publisher
- Montair
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Montair Montair WOP 0009–0155 technical data. Montair. https://montair.it/en/products/50-hz/chilled-water-close-control-units/unit-with-chillerd-water/wop-00090155/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.