Sollatek Maxima 3PH A2R 100-200 kVA Datasheet (September 2025 v2)
Original title Sollatek Maxima 3PH A2R September 2025 v2, PDF p.2
Sollatek
Sollatek Maxima 3PH A2R is a 100-200 kVA double-conversion online UPS: output power factor 0.9 (90 kW at 100 kVA), 94 percent online and over 98 percent ECO efficiency, up to 4 units in parallel.
On this page
Overview
The document is the datasheet (September 2025, v2) for the Maxima 3PH A2R series of 100, 120, 160 and 200 kVA three-phase UPS from the UK's Sollatek. The series is double-conversion online; capacities are given as 100 kVA/90 kW, 120 kVA/108 kW, 160 kVA/144 kW and 200 kVA/180 kW, so the output power factor is 0.9. Applications are data centre, telecoms, financial services, security and surveillance, automatic control, building management, manufacturing process control and petrochemical.
Electrical values: efficiency is 94 percent online and over 98 percent in ECO mode. The input is PWM IGBT-based; the voltage range is -45 to +25 percent, depending on load, around 220/380 VAC (400/415 VAC selectable), frequency 42 to 72 Hz, power factor 0.99 and THDi below 3 percent. Output voltage is nominal ±1 percent, THDv below 2 percent on linear load and crest factor at most 3:1. Overload is continuous below 105 percent, 10 minutes at 105 to 125 percent and 1 minute at 150 percent. An internal static switch (380 VAC ±15 percent) and a maintenance bypass switch are standard.
Batteries are not included: VRLA type, 36 to 40 pieces adjustable (40 by default), recharge time 8 hours to 90 percent; backup time depends on battery capacity and load. Communication: RS232, USB, 2 communication slots, 3 building alarms and EPO; optional SNMP/WEB, Modbus/Ethernet, AS400 and NMC cards. Environment: UPS 0 to 40 °C, battery 25 °C, humidity 5 to 95 percent, no derating below 1000 m. Noise is 65 to 70 dBA depending on model (70 dBA for 160 to 200 kVA). Dimensions come in two groups, 600 × 800 × 1876 mm and 600 × 830 × 1876 mm, with weights of 283, 311 and 475 kg.
The document is a technical datasheet only; standards listed are IEC/EN 62040-1, -2 and -4 and CE. A note states that physical values are approximate.
Key points
- 100, 120, 160 and 200 kVA; 90, 108, 144 and 180 kW (output power factor 0.9).
- Efficiency: 94 percent online, over 98 percent in ECO mode.
- Input: 220/380 VAC (400/415 VAC selectable), -45/+25 percent load-dependent, 42 to 72 Hz, PF 0.99, THDi below 3 percent.
- Output voltage ±1 percent, THDv below 2 percent (linear load), crest factor 3:1.
- Overload: continuous below 105 percent, 10 min at 105-125 percent, 1 min at 150 percent.
- Up to 4 units in parallel; standard static bypass (380 VAC ±15 percent) and maintenance bypass.
- Batteries not included: VRLA, 36 to 40 pieces adjustable (40 default), 8 hours to 90 percent charge.
- Noise 65 to 70 dBA; size 600 × 800 × 1876 and 600 × 830 × 1876 mm; weight 283, 311, 475 kg.
Using it in design
- Check active power in kW: with a 0.9 output power factor the 200 kVA model delivers 180 kW.
- Match the battery count (36 to 40, default 40) to the battery string; calculate autonomy separately from battery capacity.
- Weigh the over 98 percent ECO-mode efficiency against load tolerance and transfer time.
- Compare the load-dependent input voltage range (-45 percent) with battery use on a weak supply.
- Show parallel redundancy (up to 4 units) and the maintenance bypass on the single-line diagram.
Who should read it
Electrical designers and specification engineers selecting three-phase UPS for data-centre and critical facilities.
Document contents
- Description and features
- Applications
- Technical specification: input, output, bypass, battery, communication, environment, regulation, physical
- Product codes
Publication details
- Authors
- Sollatek
- Publisher
- Sollatek
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Sollatek Sollatek Maxima 3PH A2R September 2025 v2, PDF p.2. Sollatek. https://www.sollatek.com/wp-content/uploads/2025/02/Maxima-3PH-A2R-100-200kVA-Datasheet-10911070-Sep-2025-v2-1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.